Viessmann · Boiler · Domestic hot water

DHW tank heating, single boiler, standard (coding 55:0)

Vitotronic 300 GW6B

What happens, in order

  1. When the DHW tank cools below the start point, set the boiler water temperature 36 F (20 K) above the set DHW temperature.
  2. Start the DHW pump when boiler water is 14 F (7 K) above DHW temperature (coding 61:0), or start it immediately (coding 61:1).
  3. When the tank is hot, return the boiler water setpoint to the weather-compensated value.
  4. Run the DHW pump on after heating until one stop criterion is met: boiler-to-DHW difference under 13 F (7 K), weather-compensated boiler water setpoint reached, DHW temperature exceeded by 10 F (5 K), or max delay time (coding 62) reached.
  5. With coding 62:0 there is no pump delay off.

Timings and thresholds

ItemValue
Tank cold triggerSet DHW temperature -5 F (-2.5 K), change at coding 59
Tank hot triggerSet DHW temperature +5 F (+2.5 K)
Boiler water setpoint during tank heatingSet DHW temperature +36 F (+20 K), adjust at coding 60
Pump start with boiler water at factory coding 61:014 F (7 K) above DHW temperature

Applies to: Single boiler, coding 55:0

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 300 GW6B installation and service manual, p. 82. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.