Viessmann · Boiler · Domestic hot water

DHW tank heating, single boiler, adaptive (coding 55:1)

Vitotronic 300 GW6B

What happens, in order

  1. When the tank cools, raise the boiler water setpoint to 36 F (20 K) above set DHW temperature.
  2. Start the DHW pump based on boiler water temperature (coding 61:0), or immediately (coding 61:1).
  3. When the tank is hot, the control checks whether the boiler is still needed for heating or whether residual heat should go to the tank.
  4. Based on that check, the control sets burner and DHW pump stop times so the DHW temperature is not greatly overshot.

Timings and thresholds

ItemValue
Pump start with boiler water at coding 61:013 F (7 K) above DHW temperature
Tank cold triggerSet DHW temperature -5 F (-2.5 K), change at coding 59
Tank hot triggerSet DHW temperature +5 F (+2.5 K)

Applies to: Single boiler, coding 55:1

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 300 GW6B installation and service manual, p. 82. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.