Viessmann · Boiler · Domestic hot water

DHW tank heating sequence with DHW heating system (coding 55: 3)

Vitocontrol-S VD2/CT3/CM2

What happens, in order

  1. When the tank cools to the set value minus 2.5 K, raise common supply temperature 20 °C (36 °F) above the set DHW temperature.
  2. Switch the primary DHW pump ON.
  3. The three-way mixing valve opens, then regulates to the set value.
  4. The DHW pump cycles on and off until the set supply temperature is reached, then runs constantly.
  5. When the tank is hot, return common supply to the weather-compensated value.
  6. Switch the DHW pump OFF immediately if the mixing valve is open, or after the coding 62 run-on time.

Applies to: DHW heating systems with calorifier

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 134. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.