Viessmann · Boiler · Domestic hot water
DHW tank heating sequence (coding 55: 0)
What happens, in order
- When the DHW tank cools to the set value minus 2.5 K, start DHW tank heating.
- Raise the common supply temperature 20 °C (36 °F) above the set DHW temperature.
- When the tank is hot (set value +2.5 K), return the common set supply temperature to the weather-compensated value.
- Boiler temperature dependant DHW pump switching (coding 61: 10) starts the pump when boiler water is 7 K (13 °F) above DHW temperature.
Timings and thresholds
| Item | Value |
|---|---|
| DHW pump run-on | Until tank is 5 K (9 °F) above set DHW or the coding 62 time limit is reached |
Applies to: DHW tank heating, standard control
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 134. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.