Viessmann · Boiler · Domestic hot water

DHW tank heating sequence (coding 55: 0)

Vitocontrol-S VD2/CT3/CM2

What happens, in order

  1. When the DHW tank cools to the set value minus 2.5 K, start DHW tank heating.
  2. Raise the common supply temperature 20 °C (36 °F) above the set DHW temperature.
  3. When the tank is hot (set value +2.5 K), return the common set supply temperature to the weather-compensated value.
  4. Boiler temperature dependant DHW pump switching (coding 61: 10) starts the pump when boiler water is 7 K (13 °F) above DHW temperature.

Timings and thresholds

ItemValue
DHW pump run-onUntil tank is 5 K (9 °F) above set DHW or the coding 62 time limit is reached

Applies to: DHW tank heating, standard control

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 134. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.