Viessmann · Boiler · Other

DHW tank heating sequence

Vitotronic 200

What happens, in order

  1. When the DHW tank temperature falls 4.5 F / 2.5 C below setpoint (coding 59 adjustable), the boiler setpoint rises to 36 F / 20 C above the DHW setpoint (coding 60 adjustable).
  2. With coding 61:0 the DHW pump starts when boiler water exceeds DHW temperature by 12.6 F / 7 C; with 61:1 it starts at once.
  3. With priority control (coding A2:2) the supply setpoint drops to 32 F / 0 C, the mixing valve closes and heating circuit pumps stop.
  4. When the tank temperature rises 4.5 F / 2.5 C above setpoint, the boiler setpoint returns to the weather-responsive value.
  5. The DHW pump keeps running (coding 62) until boiler to DHW difference is under 12.6 F / 7 C, the boiler reaches its weather-responsive value, or DHW exceeds setpoint by 9 F / 5 C.
  6. With coding 62:0 the pump stops immediately; with 62:1 to 62:15 the switch-off delay is 1 to 15 minutes.

Timings and thresholds

ItemValue
Tank switching differential (factory)plus or minus 4.5 F / 2.5 C
Boiler lead over DHW setpoint (factory)36 F / 20 C
DHW pump switch-off delay (factory)10 minutes (maximum 15 minutes per p. 54)
Automatic program lead time before space heating30 minutes

Applies to: Tank temperature control

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 KW2 service instructions, p. 53, p. 54. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.