Viessmann · Boiler · Domestic hot water
DHW tank heating sequence
What happens, in order
- When DHW falls 2.5 C / 4.5 F below set point, the boiler set point is raised to 20 C / 36 F above the DHW set point.
- With coding 61 1, the DHW pump starts immediately.
- With coding 61 0, the DHW pump starts only when boiler water is 7 C / 13 F above the DHW temperature.
- When DHW rises 2.5 C / 4.5 F above set point, the boiler set point returns to the boiler circuit set point.
- With coding 62 10, the DHW pump keeps running until boiler and DHW temperatures are within 7 C / 13 F, or the boiler circuit set point is reached, or DHW exceeds its set point by 5 C / 9 F.
- With coding 62 00, the DHW pump stops immediately.
- With adaptive DHW heating (coding 55 1), the control unit sets burner and pump switch-off times so DHW does not overshoot much after heating.
Timings and thresholds
| Item | Value |
|---|---|
| DHW pump run-on maximum | 15 minutes (coding 62) |
Applies to: Vitotronic 100 GC1 DHW heating
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 installation and service instructions, p. 107. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.