Viessmann · Boiler · Domestic hot water
DHW tank heating, primary store system (code 55:3)
What happens, in order
- When the tank goes cold, set supply temperature 20 K above set DHW temperature.
- Start the primary pump in the primary store system.
- Open the 3-way mixing valve, then regulate it to the set value.
- Cycle the DHW circulation pump on and off until supply reaches set DHW temperature plus 5 K, then run it continuously.
- When the tank is hot, stop the DHW pump once the 3-way valve is fully open, or after the run-on time set at code 62.
Timings and thresholds
| Item | Value |
|---|---|
| Target supply temp | Set DHW temperature + 5 K |
Codes you may see during this
55:3; 4C:1; 4E:2; 62
Applies to: Primary store systems
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 86. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.