Viessmann · Boiler · Domestic hot water
DHW tank heating in cascade control (coding 55:0 and 55:1)
What happens, in order
- When the tank cools, set the common supply temperature 36 F (20 K) above set DHW temperature.
- When the tank is hot, return the common supply temperature to the weather-compensated value.
- With pump delay off, the DHW pump runs on until DHW temperature is exceeded by 9 F (5 K) or the max delay time (coding 62) is reached.
- With coding 55:1 the control checks residual boiler heat and sets burner and circulation pump stop times to limit overshoot.
Timings and thresholds
| Item | Value |
|---|---|
| Common supply setpoint during tank heating | Set DHW temperature +36 F (+20 K) |
| Overshoot limit before pump stops | DHW temperature exceeded by 9 F (5 K) |
Applies to: Cascade control, coding 55:0 or 55:1
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 300 GW6B installation and service manual, p. 83. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.