DHW tank heating in cascade control (coding 55:0 and 55:1)

Vitotronic 300 GW6B

What happens, in order

  1. When the tank cools, set the common supply temperature 36 F (20 K) above set DHW temperature.
  2. When the tank is hot, return the common supply temperature to the weather-compensated value.
  3. With pump delay off, the DHW pump runs on until DHW temperature is exceeded by 9 F (5 K) or the max delay time (coding 62) is reached.
  4. With coding 55:1 the control checks residual boiler heat and sets burner and circulation pump stop times to limit overshoot.

Timings and thresholds

ItemValue
Common supply setpoint during tank heatingSet DHW temperature +36 F (+20 K)
Overshoot limit before pump stopsDHW temperature exceeded by 9 F (5 K)

Applies to: Cascade control, coding 55:0 or 55:1

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 300 GW6B installation and service manual, p. 83. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.