DHW tank heating, adaptive control (code 55:1)
What happens, in order
- When the tank goes cold, set supply temperature 20 K above set DHW temperature.
- When the tank is hot, the control checks whether the boiler is needed for heating after DHW heating or whether residual heat should go to the tank.
- The control sets burner and pump stop times to avoid overshooting the set DHW temperature.
Codes you may see during this
55:1
Applies to: DHW tanks
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 86. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.