Viessmann · Boiler · Domestic hot water

DHW priority control for heating circuits

Vitotronic 300 GW6B

What happens, in order

  1. With priority control (coding a2:2): during tank heating the heating circuit set supply is dropped to 32°F (0°C), the mixing valve closes and the heating circuit pump switches off.
  2. Without priority control the heating circuit keeps the same set value during tank heating.
  3. With modulating priority and a mixing valve: the heating circuit pump stays on. The circuit supply is reduced until the set boiler water temperature is reached. The reduction depends on outdoor temperature, boiler water deviation, heating curve slope and shift, and coding a2.

Applies to: Heating circuit control unit with DHW

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW6B installation and service instructions, p. 78. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.