Viessmann · Boiler · Domestic hot water
DHW mode with post-purge
What happens, in order
- The space heating pump is turned off.
- The DHW pump runs while the DHW aquastat or set-point control calls.
- The boiler receives a DHW demand and modulates to a higher boiler water temperature.
- If a room thermostat call also exists, priority switches to DHW until the DHW demand is satisfied, then back to space heating.
- When the DHW call ends, the post-purge timer counts down and resets during any DHW call.
- When the post-purge timer reaches zero, the DHW pump turns off and the unit returns to normal mode.
Timings and thresholds
| Item | Value |
|---|---|
| DHW pump post-purge timer (switch 1 ON) | 60 seconds (switch 2 ON) or 120 seconds (switch 2 OFF) |
Applies to: Versatronik 10.WB1 with Vitodens 100-W WB1A/B
Models
Versatronik 10.WB1
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 10.WB1 installation and operating manual, pp. 21-23. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.