Viessmann · Boiler · Domestic hot water

DHW mode with post-purge

Versatronik 10.WB1

What happens, in order

  1. The space heating pump is turned off.
  2. The DHW pump runs while the DHW aquastat or set-point control calls.
  3. The boiler receives a DHW demand and modulates to a higher boiler water temperature.
  4. If a room thermostat call also exists, priority switches to DHW until the DHW demand is satisfied, then back to space heating.
  5. When the DHW call ends, the post-purge timer counts down and resets during any DHW call.
  6. When the post-purge timer reaches zero, the DHW pump turns off and the unit returns to normal mode.

Timings and thresholds

ItemValue
DHW pump post-purge timer (switch 1 ON)60 seconds (switch 2 ON) or 120 seconds (switch 2 OFF)

Applies to: Versatronik 10.WB1 with Vitodens 100-W WB1A/B

Models

Versatronik 10.WB1

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 10.WB1 installation and operating manual, pp. 21-23. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.