Viessmann · Boiler · Domestic hot water

DHW heating sequence (single boiler with Therm-Control)

Vitorond 200 VD2A

What happens, in order

  1. DHW heating starts when tank temperature falls below the set DHW temperature, if the time switch enables tank heating.
  2. Boiler water is raised to the set DHW temperature plus 20 K.
  3. The tank primary pump starts once boiler water is 7 K above the actual DHW temperature.
  4. If absolute priority is enabled, heating circuit pumps M2 and M3 are switched off and mixing valves close.
  5. If modulating priority is enabled, pumps M2 and M3 keep running and mixing valves close only far enough to reach the tank heating boiler water temperature.

Timings and thresholds

ItemValue
Boiler water target above set DHW temperature+20 K (36 F)
Boiler water lead before tank primary pump starts7 K (12.6 F)

Applies to: Single boiler system with Therm-Control

Models

Vitorond 200 VD2A 125 to 270

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2A Technical Data Manual, p. 19. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.