Viessmann · Boiler · Standby/shutdown

Delayed pump switch-off and pump protection

Versatronik 200

What happens, in order

  1. When a pump is due to switch off, it keeps running for 5 minutes if a burner ran in the last 5 minutes before switch-off.
  2. Pump blocking protection every day at 12:00 all pumps not run in the past 24 hours switch on for 5 seconds.
  3. Mixing valve protection if the valve has not moved for 24 hours, it is fully opened at about 03:00 (once). The heating circuit pump is off during this time.
  4. The maximum flow temperature is monitored; this protection is cancelled at maximum flow minus 5 K.

Timings and thresholds

ItemValue
Delayed pump switch-off5 minutes
Pump blocking protection5 seconds at 12:00 daily
Mixing valve protectionFully opened at about 03:00 after 24 hours without movement

Applies to: Versatronik 200 circulation pumps and mixing valves

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 200 Installation and Operating Manual, p. 156. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.