Viessmann · Boiler · Standby/shutdown
Delayed pump switch-off and pump protection
What happens, in order
- When a pump is due to switch off, it keeps running for 5 minutes if a burner ran in the last 5 minutes before switch-off.
- Pump blocking protection every day at 12:00 all pumps not run in the past 24 hours switch on for 5 seconds.
- Mixing valve protection if the valve has not moved for 24 hours, it is fully opened at about 03:00 (once). The heating circuit pump is off during this time.
- The maximum flow temperature is monitored; this protection is cancelled at maximum flow minus 5 K.
Timings and thresholds
| Item | Value |
|---|---|
| Delayed pump switch-off | 5 minutes |
| Pump blocking protection | 5 seconds at 12:00 daily |
| Mixing valve protection | Fully opened at about 03:00 after 24 hours without movement |
Applies to: Versatronik 200 circulation pumps and mixing valves
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 200 Installation and Operating Manual, p. 156. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.