Viessmann · Boiler · Cooling

Cooling operation sequence

Versatronik 200

What happens, in order

  1. Cooling operation actuates the switch-over valve to cooling.
  2. Heating operation is disabled; hot water preparation still runs.
  3. Refrigerating machines start if required by a heating circuit or when the temperature exceeds the Installation/T-Return Cooling value.
  4. Heating circuits are controlled to the Heating circuit x/T-Flow Cooling temperature.
  5. If the MF function 'cooling switch-over valve' is active, the cooling circuit is hydraulically separated.

Applies to: Versatronik 200 System Control, cooling operation

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 200 manual, p. 68. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.