Viessmann · Boiler · Cooling

Cooling mode enable and refrigerating machine control

Versatronik 200

What happens, in order

  1. Cooling mode can be selected with the operating mode selector when a refrigerating machine is present. Hot water loading is then only possible from conventional heat generators.
  2. The bypass valve for cooling (MF) is switched in cooling mode if activated.
  3. Refrigerating machines and HS pumps start when the heating circuits require it, until the return temperature drops below the desired cooling return temperature (Des return t cool). Switching hysteresis is 2 K.
  4. Weather-dependent cooling cooling is enabled when outdoor temperature exceeds Min TO cooling and ends 1 K below the limit.
  5. Room-dependent cooling cooling is enabled when room temperature exceeds Room t cool and ends 2 K below the set temperature.

Timings and thresholds

ItemValue
Refrigerating machine switching hysteresis2 K
Weather cooling reset1 K below limit
Room cooling reset2 K below set temperature

Applies to: Versatronik 200 with refrigerating machine

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 200 Installation and Operating Manual, p. 157. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.