Viessmann · Boiler · Heating

Condensing strategy start and stop

Vitotronic 200Vitotronic 300-K

What happens, in order

  1. The aim is to run as many boilers as possible at the lowest output level.
  2. An additional boiler starts when the required output can be met by the active boilers plus the next boiler in the sequence.
  3. Boilers are started via an output statement (code "3D:1").
  4. Boilers shut down when the shutdown integral exceeds the limit set by coding address "46"; the boiler started last is shut down first.

Codes you may see during this

3C:0; 3D:1; 46

Applies to: Vitotronic 300-K

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 and 300-K installation and service instructions, p. 80. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.