Combustion self-calibration after burner start

Vitodens 200-W B2HB

What happens, in order

  1. After the burner starts, the system briefly runs at maximum ionization current, which corresponds to air factor λ=1.
  2. The calibration runs for about 5 seconds, then the combustion is regulated.
  3. The combustion management system adjusts the air factor to between λ=1.24 and 1.44 for optimum combustion.
  4. The electronic gas valve then meters gas to suit the gas quality.
  5. The calibration repeats after each power failure or shutdown.

Timings and thresholds

ItemValue
Self-calibration duration after burner startapproximately 5 seconds

Applies to: Vitodens 200-W B2HB Lambda Pro combustion management

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 33. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.