Viessmann · Boiler · Ignition
Combustion self-calibration after burner start
What happens, in order
- After the burner starts, the system briefly runs at maximum ionization current, which corresponds to air factor λ=1.
- The calibration runs for about 5 seconds, then the combustion is regulated.
- The combustion management system adjusts the air factor to between λ=1.24 and 1.44 for optimum combustion.
- The electronic gas valve then meters gas to suit the gas quality.
- The calibration repeats after each power failure or shutdown.
Timings and thresholds
| Item | Value |
|---|---|
| Self-calibration duration after burner start | approximately 5 seconds |
Applies to: Vitodens 200-W B2HB Lambda Pro combustion management
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 33. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.