Viessmann · Boiler · Other

Combustion air demand sequence

Versatronik 300 Cascade Control

What happens, in order

  1. Common supply temperature drops below set point. The Versatronik 300 sends a set point demand to the first boiler and the AUX output turns on.
  2. The AUX output triggers the combustion or exhaust air system.
  3. The Versatronik 300 waits for the BMS or mechanical feedback on the INT input before the boilers receive heat demand.
  4. If the combustion air signal is not sensed within the time limit, the control gives a fault output.

Timings and thresholds

ItemValue
Combustion air input signal timeout60 minutes (can be changed from factory value)

Applies to: Versatronik 300 with combustion air interlock

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 300 Cascade Control V1.4 manual, p. 23. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.