Viessmann · Boiler · Standby/shutdown
Circulation pump switch-off by demand and temperature limits
What happens, in order
- Demand-dependent control switches the pumps off when there is no heating demand, and closes the mixing valves at the same time.
- Room control pumps switch off when room temperature exceeds the desired temperature.
- Weather control pumps switch off when outdoor temperature exceeds the room setpoint or flow setpoint drops below 20 °C.
- Temp limits control pumps and mixing valves switch off when outdoor temperature exceeds the heating limit, and restart when it drops 1 K below the limit.
- If the room factor is 0, the pump keeps running through the reduced period after a one-off heating demand.
Timings and thresholds
| Item | Value |
|---|---|
| Temp limit restart | 1 K below heating limit |
Applies to: Versatronik 200 heating circuits
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 200 Installation and Operating Manual, p. 156. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.