Viessmann · Boiler · Standby/shutdown

Circulation pump switch-off by demand and temperature limits

Versatronik 200

What happens, in order

  1. Demand-dependent control switches the pumps off when there is no heating demand, and closes the mixing valves at the same time.
  2. Room control pumps switch off when room temperature exceeds the desired temperature.
  3. Weather control pumps switch off when outdoor temperature exceeds the room setpoint or flow setpoint drops below 20 °C.
  4. Temp limits control pumps and mixing valves switch off when outdoor temperature exceeds the heating limit, and restart when it drops 1 K below the limit.
  5. If the room factor is 0, the pump keeps running through the reduced period after a one-off heating demand.

Timings and thresholds

ItemValue
Temp limit restart1 K below heating limit

Applies to: Versatronik 200 heating circuits

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 200 Installation and Operating Manual, p. 156. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.