Viessmann · Boiler · Other

Changeover between heating season and cooling season

Vitodens 200-W B2HB

What happens, in order

  1. For the cooling season, close valve v1 and open valve v2.
  2. For the heating season, close valve v2 and open valve v1.
  3. Label valves v1 and v2 as recommended.
  4. Run the circulating pump from its own on/off switch, not from the boiler pump aquastat.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199 in heating/cooling applications

Models

4557160199

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB installation instructions, p. 44. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.