Viessmann · Boiler · Heating
Cascade standalone control: sensor and no-sensor start/stop logic
What happens, in order
- With a supply temperature sensor, set coding 3b:1 or 3b:3 (Cascade group). Start and stop use the deviation between set and actual supply temperature.
- Without a supply temperature sensor, set coding 3b:0 or 3b:2. Start and stop use the set boiler water temperature compared with the estimated average actual boiler water temperature of active boilers.
- Only boilers with open motorized isolation valves are counted.
- In the sequential control mode, set coding 3b:4 with a supply sensor. The control strategy is then set automatically to conventional boiler strategy 2 (3c:2).
Applies to: Cascade control unit, standalone and sequential control
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW6B installation and service instructions, p. 73. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.