Viessmann · Boiler · Heating

Cascade standalone control: sensor and no-sensor start/stop logic

Vitotronic 300 GW6B

What happens, in order

  1. With a supply temperature sensor, set coding 3b:1 or 3b:3 (Cascade group). Start and stop use the deviation between set and actual supply temperature.
  2. Without a supply temperature sensor, set coding 3b:0 or 3b:2. Start and stop use the set boiler water temperature compared with the estimated average actual boiler water temperature of active boilers.
  3. Only boilers with open motorized isolation valves are counted.
  4. In the sequential control mode, set coding 3b:4 with a supply sensor. The control strategy is then set automatically to conventional boiler strategy 2 (3c:2).

Applies to: Cascade control unit, standalone and sequential control

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW6B installation and service instructions, p. 73. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.