Viessmann · Boiler · Heating
Cascade on and off sequence
What happens, in order
- As common supply or LLH temperature drops below set point, a call for heat goes to the lead boiler.
- The call starts about 2C below set point. The boiler control compares the set point with its water temperature and decides whether to fire.
- The pump runs and boiler water temperature drops, so the burner fires.
- The boiler modulates by its own internal PID.
- If the running boiler exceeds the Maximum Boiler Mod setting, the next boiler gets the set point and modulates on its own.
- If common supply drops below the Stage On margin, another boiler is forced on.
- As common supply rises, boilers modulate down. If average modulation of active boilers is at or below Minimum Boiler Mod, a boiler is staged off after a 2 minute delay.
- Boilers may stage off when they have modulated down and shut off but still have a call for heat.
Timings and thresholds
| Item | Value |
|---|---|
| Call for heat relative to set point | About 2C below set point |
| Stage off delay | 2 minutes |
| Stage On adjustment range | 5C/41F to 30C/86F |
| Stage Down adjustment range | 5C/41F to 30C/86F |
Applies to: Versatronik 300 cascade control
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 300 Cascade Control manual, p. 35. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.