Viessmann · Boiler · Heating

Cascade on and off sequence

Versatronik 300

What happens, in order

  1. As common supply or LLH temperature drops below set point, a call for heat goes to the lead boiler.
  2. The call starts about 2C below set point. The boiler control compares the set point with its water temperature and decides whether to fire.
  3. The pump runs and boiler water temperature drops, so the burner fires.
  4. The boiler modulates by its own internal PID.
  5. If the running boiler exceeds the Maximum Boiler Mod setting, the next boiler gets the set point and modulates on its own.
  6. If common supply drops below the Stage On margin, another boiler is forced on.
  7. As common supply rises, boilers modulate down. If average modulation of active boilers is at or below Minimum Boiler Mod, a boiler is staged off after a 2 minute delay.
  8. Boilers may stage off when they have modulated down and shut off but still have a call for heat.

Timings and thresholds

ItemValue
Call for heat relative to set pointAbout 2C below set point
Stage off delay2 minutes
Stage On adjustment range5C/41F to 30C/86F
Stage Down adjustment range5C/41F to 30C/86F

Applies to: Versatronik 300 cascade control

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 300 Cascade Control manual, p. 35. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.