Viessmann · Boiler · Heating

Cascade conventional boiler strategy 2 (coding 3c:2, factory setting)

Vitotronic 300 GW6B

What happens, in order

  1. Aim long burner run times.
  2. Extra boiler starts only when all active burners at maximum output still cannot reach the set supply temperature. Start is checked against coding 45 (Cascade group).
  3. A boiler shuts down if the burners were ramped to minimum output because of a large negative deviation and output is still too high.
  4. Shutdown the shutdown integral is checked against coding 46 (Cascade group). When exceeded, the boiler started last shuts down.
  5. Example in the manual two modulating boilers, each 100% rated output with base load set to 33%.

Applies to: Cascade control unit, conventional boilers, factory default

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW6B installation and service instructions, p. 76. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.