Cascade conventional boiler strategy 2 (coding 3c:2, factory setting)
What happens, in order
- Aim long burner run times.
- Extra boiler starts only when all active burners at maximum output still cannot reach the set supply temperature. Start is checked against coding 45 (Cascade group).
- A boiler shuts down if the burners were ramped to minimum output because of a large negative deviation and output is still too high.
- Shutdown the shutdown integral is checked against coding 46 (Cascade group). When exceeded, the boiler started last shuts down.
- Example in the manual two modulating boilers, each 100% rated output with base load set to 33%.
Applies to: Cascade control unit, conventional boilers, factory default
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW6B installation and service instructions, p. 76. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.