Viessmann · Boiler · Heating

Cascade conventional boiler strategy 1 (coding 3c:1)

Vitotronic 300 GW6B

What happens, in order

  1. Aim keep as few boilers running as possible, and run conventional boilers high in their output range to avoid condensate from low return temperature.
  2. Start starting integral is checked against coding 45 (Cascade group). The next boiler in sequence starts when the value is exceeded.
  3. Shutdown a boiler shuts down when the output reduction (coding 3d:1) shows the demand can be met without the boiler started last.
  4. Example in the manual two modulating boilers, each 100% rated output with base load set to 33%.

Applies to: Cascade control unit, conventional boilers

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW6B installation and service instructions, p. 75. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.