Viessmann · Boiler · Heating
Cascade conventional boiler strategy 1 (coding 3c:1)
What happens, in order
- Aim keep as few boilers running as possible, and run conventional boilers high in their output range to avoid condensate from low return temperature.
- Start starting integral is checked against coding 45 (Cascade group). The next boiler in sequence starts when the value is exceeded.
- Shutdown a boiler shuts down when the output reduction (coding 3d:1) shows the demand can be met without the boiler started last.
- Example in the manual two modulating boilers, each 100% rated output with base load set to 33%.
Applies to: Cascade control unit, conventional boilers
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW6B installation and service instructions, p. 75. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.