Viessmann · Boiler · Heating

Cascade control strategy example (two boilers, modulating burner)

Vitotronic 100 GC1Vitocontrol-S VD2/CT3/CM2

What happens, in order

  1. Both example boilers are 100 kW rated output with the basic load set to 33 %.
  2. Gross calorific strategy (coding 3C 0): the lead boiler starts first and the second boiler follows as the load rises.
  3. Net calorific strategy 1 (coding 3C 1): same staging logic, with the boiler load steps shown on the page.
  4. Net calorific strategy 2 (coding 3C 2): alternative staging per the strategy chart on page 129.
  5. Check the rated output versus total load on the chart to confirm the staging matches the system.

Applies to: Two boiler cascade with modulating burners

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 128. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.