Viessmann · Boiler · Heating

Cascade control: set supply temperature and common limits

Vitotronic 300 GW6B

What happens, in order

  1. The cascade control sets the supply temperature by starting or stopping burners, or individual burner stages.
  2. The set supply temperature comes from the heating circuit without mixing valve (A1), the heating circuits with mixing valves (M2, M3), other consumers, the DHW target, and external demands.
  3. Upper limit is the maximum system supply temperature (coding 37, Cascade group).
  4. Lower limit is the minimum system supply temperature (coding 36, Cascade group).
  5. Boilers in parallel use standalone control. Boilers in series use the same control principle as parallel.

Applies to: Cascade control unit

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW6B installation and service instructions, p. 73. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.