Viessmann · Boiler · Heating

Cascade control sequence (stand-alone)

Vitotronic 200Vitotronic 300-K

What happens, in order

  1. Boilers are connected in parallel on a common flow, with or without a supply temperature sensor.
  2. The cascade control sets the boiler water temperature for all active boilers; each Vitotronic 200 regulates to that set point.
  3. With a supply sensor, start and shutdown use the deviation between set and actual supply temperature.
  4. Without a supply sensor, start and shutdown use the set boiler water temperature and the estimated average actual boiler water temperature of running boilers.
  5. With flue gas cascade under positive pressure (code "7E:1"), all active burners are briefly ramped above 80% when another boiler starts.
  6. Select one condensing strategy or one of two conventional boiler strategies (coding address "3C").

Codes you may see during this

7E:1; 3B:0; 3B:1; 3C

Applies to: Vitotronic 300-K

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 and 300-K installation and service instructions, p. 79. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.