Viessmann · Boiler · Heating
Cascade control sequence (stand-alone)
What happens, in order
- Boilers are connected in parallel on a common flow, with or without a supply temperature sensor.
- The cascade control sets the boiler water temperature for all active boilers; each Vitotronic 200 regulates to that set point.
- With a supply sensor, start and shutdown use the deviation between set and actual supply temperature.
- Without a supply sensor, start and shutdown use the set boiler water temperature and the estimated average actual boiler water temperature of running boilers.
- With flue gas cascade under positive pressure (code "7E:1"), all active burners are briefly ramped above 80% when another boiler starts.
- Select one condensing strategy or one of two conventional boiler strategies (coding address "3C").
Codes you may see during this
7E:1; 3B:0; 3B:1; 3C
Applies to: Vitotronic 300-K
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 and 300-K installation and service instructions, p. 79. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.