Viessmann · Boiler · Other

Cascade control, conventional boiler strategy 2 (code 3C:2)

Vitotronic 200Vitotronic 300-K

What happens, in order

  1. Start an extra boiler only when the maximum output of all active burners cannot reach the set supply temperature.
  2. Start the next boiler in sequence when the starting integral exceeds the limit set at coding address 45.
  3. Return burners to minimum output on a large negative control deviation.
  4. Shut a boiler down if output is still too high after burners return to minimum.
  5. Shutdown is controlled by the shutdown integral; when it exceeds the limit at coding address 46, the boiler started last is shut down.

Codes you may see during this

3C:2; 45; 46

Applies to: Cascade systems

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 81. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.