Viessmann · Boiler · Other
Cascade control, condensing strategy (code 3C:0)
What happens, in order
- Run as many boilers as possible at the lowest output level.
- Start a boiler with an output statement (code 3D:1).
- Start an extra boiler only when the required output can be met by the active boilers plus the next boiler in the sequence.
- Shut boilers down using the shutdown integral.
- When the shutdown integral exceeds the limit set at coding address 46, shut down the boiler that started last.
Codes you may see during this
3C:0; 3D:1; 46
Applies to: Cascade systems, e.g. 2 Vitodens 200-W
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 80. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.