Cascade control, condensing strategy (code 3C:0)

Vitotronic 200Vitotronic 300-K

What happens, in order

  1. Run as many boilers as possible at the lowest output level.
  2. Start a boiler with an output statement (code 3D:1).
  3. Start an extra boiler only when the required output can be met by the active boilers plus the next boiler in the sequence.
  4. Shut boilers down using the shutdown integral.
  5. When the shutdown integral exceeds the limit set at coding address 46, shut down the boiler that started last.

Codes you may see during this

3C:0; 3D:1; 46

Applies to: Cascade systems, e.g. 2 Vitodens 200-W

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 80. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.