Viessmann · Boiler · Heating

Cascade condensing strategy (coding 3c:0)

Vitotronic 300 GW6B

What happens, in order

  1. Aim run as many boilers as possible at the lowest output, to get the condensing effect and long burner run times.
  2. Start an extra boiler starts when the current demand can be covered by the active boilers plus the next boiler in the sequence.
  3. Shutdown the shutdown integral is checked against the limit at coding 46 (Cascade group). When exceeded, the boiler started last shuts down.
  4. Example in the manual two modulating boilers, each 100% rated output with base load set to 33%.

Applies to: Cascade control unit, condensing boilers

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW6B installation and service instructions, p. 74. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.