Viessmann · Boiler · Ignition

Burner switch-on and switch-off

Vitotronic 300

What happens, in order

  1. When boiler water temperature falls, the control sends a burner on signal at a boiler setpoint of -2°C / -4°F.
  2. The burner starts its own monitoring program.
  3. Burner override may be delayed by a few minutes depending on the additional controls and firing method.
  4. The burner switches off when the boiler temperature rises past the switch-off differential set in coding 13.

Timings and thresholds

ItemValue
Burner override delayA few minutes, depending on system

Applies to: Vitotronic 300 GW2

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 installation and service instructions, p. 86. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.