Viessmann · Boiler · Standby/shutdown

Burner shutdown, gas valve proof of closure and post-purge

Vitodens 200-W

What happens, in order

  1. Phase 7 after any normal or uncontrolled shutdown, the flame safeguard runs a full mechanical and electrical gas valve proof of closure test.
  2. After a successful test, the flame must not be present. If flame existed for more than 15 seconds, the flame safeguard locks out permanently.
  3. Phase 8 both gas valves close and post-purge speed test runs; call for heat ends.
  4. Phase 9 if the fixed high limit trips in normal operation, the blower purges for 15 minutes to cool the heat exchanger.

Timings and thresholds

ItemValue
Flame present after shutdown before permanent lockoutmore than 15 seconds
High limit post-purge15 minutes

Applies to: Burner shutdown

Models

B2HB 45B2HB 57B2HB 160B2HB 199

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB service manual, p. 93. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.