Viessmann · Boiler · Ignition

Burner program sequence of operation (startup)

Vitodens 200-W

What happens, in order

  1. Phase 0 standby. Gas valve and blower are off until a call for heat.
  2. Phase 1 blower stand-still check. Blower speed must be below 300 rpm within 51 seconds.
  3. Phase 2 pre-purge speed test. Controller checks blower max rpm with fan speed controller.
  4. Phase 3 pre-purge. Runs on the programmed timing; fan speed must be within the requested range.
  5. Phase 4 pre-ignition. Ignition spark starts and is controlled.
  6. Phase 5 ignition and flame stabilization. Gas valve opens during the 4.5 second safety timing. Flame must be detected; the phase ends in under 1.5 seconds once flame is seen. After 3 failed trials the burner locks out and needs manual reset.
  7. Phase 6 modulation or calibration. Modulation release comes after the 4.5 second stabilization. Forced shutdown after 24 hours of continuous operation. Controller may start automatic calibration.

Timings and thresholds

ItemValue
Blower stand-still checkbelow 300 rpm within 51 seconds
Safety timing, gas valve open4.5 seconds
Flame detected to phase endunder 1.5 seconds
Ignition trials before lockout3
Forced shutdownafter 24 hours continuous operation

Applies to: Burner startup

Models

B2HB 45B2HB 57B2HB 160B2HB 199

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB service manual, p. 93. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.