Viessmann · Boiler · Heating

Burner on/off switching based on boiler water temperature

Vitotronic 200

What happens, in order

  1. The burner is controlled by the boiler water temperature with a switching hysteresis (coding address 04).
  2. When the boiler water temperature falls to 3.6 F / 2 C below setpoint, the burner switch-on signal is set and the burner starts its own monitoring program.
  3. Depending on the additional control functions and firing method, burner start can be delayed by a few minutes.
  4. When the boiler water temperature rises to 3.6 F / 2 C above setpoint, the burner switches off.
  5. With heat demand controlled hysteresis, the burner run time changes with heat demand: a low heat demand gives a longer off time and a high heat demand gives a shorter one.

Timings and thresholds

ItemValue
Switching differential at deliveryplus or minus 3.6 F / 2 C
Fixed switching hysteresis (coding 04: 0)7 F / 4 C
Heat demand hysteresis, ERB50 functionabout 11 to 21.6 F / 6 to 12 C
Heat demand hysteresis, ERB80 function11 to 36 F / 6 to 20 C
Burner cycling (coding 28: 1)Burner on for 30 seconds every 5 hours

Applies to: Burner switching in boiler temperature control

Models

Vitotronic 200 KW2

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 200 service instructions, p. 45. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.