Boiler water temperature control

Vitotronic 300, GW6B

What happens, in order

  1. The burner modulates to regulate boiler water temperature.
  2. The set boiler water temperature comes from the set supply temperature of the heating circuits (own and LON-linked), the external demand, and the DHW temperature target.
  3. When the DHW tank is heated, the default set boiler water temperature is 20 K (36 F) above the set DHW temperature. This is adjustable via coding 60 in the DHW group.

Applies to: Single boiler and multi boiler systems

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300, GW6B installation and service instructions, p. 72. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.