Viessmann · Boiler · Heating
Boiler water temperature control
What happens, in order
- The burner modulates to regulate boiler water temperature.
- The set boiler water temperature comes from the set supply temperature of the heating circuits (own and LON-linked), the external demand, and the DHW temperature target.
- When the DHW tank is heated, the default set boiler water temperature is 20 K (36 F) above the set DHW temperature. This is adjustable via coding 60 in the DHW group.
Applies to: Single boiler and multi boiler systems
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300, GW6B installation and service instructions, p. 72. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.