Viessmann · Boiler · Heating
Boiler water temperature control (weather-responsive)
What happens, in order
- The desired boiler water temperature follows its own heating curve based on outdoor temperature.
- With one mixing valve circuit only, the boiler setpoint is held 14 F / 8 C above the desired supply temperature.
- With a non-mixing circuit and a mixing circuit together, the boiler setpoint follows its own curve, with the 14 F / 8 C difference factory preset.
- The differential temperature can be changed with coding 05 (range 0 to 72 F / 0 to 40 C).
- The boiler water temperature is limited between its minimum and the maximum set by the heating curve.
Timings and thresholds
| Item | Value |
|---|---|
| Factory differential temperature | 14 F / 8 C |
| Heating curve slope, boiler circuit | 1.8 |
| Heating curve slope, mixing valve circuit | 1.2 |
Applies to: Boiler temperature control with heating circuits
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 KW2 service instructions, p. 48. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.