Viessmann · Boiler · Heating

Boiler water temperature control on Vitotronic 200

Vitotronic 200Vitotronic 300-K

What happens, in order

  1. The Vitotronic 300-K sets the boiler water temperature to be held.
  2. On a cold boiler, the burner start point is the set boiler water temperature minus 4 K.
  3. The burner then runs its own monitoring program.
  4. The burner start can be delayed by several minutes.
  5. Once the boiler is hot, the burner shuts down at the shutdown differential of 8 K.

Timings and thresholds

ItemValue
Burner start offset below set boiler water temperature4 K
Burner shutdown differential8 K
Burner start delayseveral minutes (adjustable)

Applies to: Vitotronic 200

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 and 300-K installation and service instructions, p. 78. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.