Viessmann · Boiler · Heating

Boiler water temperature control and burner switching

Vitotronic 100

What happens, in order

  1. The burner is switched on and off to hold the boiler water temperature at its set point.
  2. The set point comes from the boiler circuit supply setpoint, any heating circuits with mixing valves, the fixed setpoint in coding 9b, and the DHW set point.
  3. With Therm-Control, the boiler set point is raised when the Therm-Control sensor reads below its set point.
  4. Three sensors in one multiple sensor well monitor the boiler water: the fixed high limit (FHL), the adjustable high limit (AHL) and the boiler temperature sensor (BTS).
  5. Burner override is requested at a boiler water set point of -2 C / -4 F. The burner then runs its own monitoring program. Depending on the system and firing method, override can be delayed by a few minutes.
  6. The burner switches off when the boiler water temperature rises above the set point plus the switch-off differential set in coding 13.

Timings and thresholds

ItemValue
Burner override trigger set point-2 C / -4 F boiler water set point
Burner override delayUp to a few minutes, depending on system and firing method

Applies to: Vitotronic 100 GC1 boiler temperature control

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 installation and service instructions, p. 105. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.