Viessmann · Boiler · Heating
Boiler water temperature control and burner switching
What happens, in order
- The burner is switched on and off to hold the boiler water temperature at its set point.
- The set point comes from the boiler circuit supply setpoint, any heating circuits with mixing valves, the fixed setpoint in coding 9b, and the DHW set point.
- With Therm-Control, the boiler set point is raised when the Therm-Control sensor reads below its set point.
- Three sensors in one multiple sensor well monitor the boiler water: the fixed high limit (FHL), the adjustable high limit (AHL) and the boiler temperature sensor (BTS).
- Burner override is requested at a boiler water set point of -2 C / -4 F. The burner then runs its own monitoring program. Depending on the system and firing method, override can be delayed by a few minutes.
- The burner switches off when the boiler water temperature rises above the set point plus the switch-off differential set in coding 13.
Timings and thresholds
| Item | Value |
|---|---|
| Burner override trigger set point | -2 C / -4 F boiler water set point |
| Burner override delay | Up to a few minutes, depending on system and firing method |
Applies to: Vitotronic 100 GC1 boiler temperature control
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 installation and service instructions, p. 105. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.