Viessmann · Boiler · Freeze protection
Boiler, sensor and room frost protection
What happens, in order
- Boiler frost protection if boiler temperature drops below 5 °C, the boiler is switched on until the boiler minimum temperature (Boiler 1 t min) is exceeded.
- Flow or storage sensor frost protection if flow or storage temperature drops below 7 °C, only the relevant pump is switched on, and it stops when the temperature rises above 9 °C.
- Room sensor frost protection if room temperature drops below 5 °C, the room setpoint is set to 5 °C, the pumps are switched on and a heat request is sent to the boiler.
Timings and thresholds
| Item | Value |
|---|---|
| Boiler frost protection trigger | below 5 °C |
| Sensor frost protection trigger | below 7 °C |
| Sensor frost protection release | above 9 °C |
Applies to: Versatronik 200
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 200 Installation and Operating Manual, p. 155. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.