Boiler deactivation when activation contact opens
What happens, in order
- Open the boiler activation contact on plug aVH.
- The isolation valve starts closing after the delay.
- No external burner override is possible and minimum temperature is no longer held.
Timings and thresholds
| Item | Value |
|---|---|
| Isolation valve closes after activation contact opens | approx. 5 minutes (coding 2C) |
Applies to: VD2/VD2A/CT3/CM2
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100, GC1 installation manual, p. 60. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.