Viessmann · Boiler · Standby/shutdown

Boiler deactivation when activation contact opens

Vitotronic 100GC1

What happens, in order

  1. Open the boiler activation contact on plug aVH.
  2. The isolation valve starts closing after the delay.
  3. No external burner override is possible and minimum temperature is no longer held.

Timings and thresholds

ItemValue
Isolation valve closes after activation contact opensapprox. 5 minutes (coding 2C)

Applies to: VD2/VD2A/CT3/CM2

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100, GC1 installation manual, p. 60. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.