AUX output as heat demand
What happens, in order
- Turn on AUX when all non-faulted, non-ECO lock boilers are running and set point still cannot be met.
- AUX turns on when common supply temperature drops below set point by the differential, and stays below it for the configured time.
- Once on, AUX stays on for the minimum run time.
- AUX turns off when the common supply temperature is satisfied, or when either non-faulted, non-ECO lock boiler stages off.
Timings and thresholds
| Item | Value |
|---|---|
| AUX minimum run time | 1 to 99 min (setup menu) |
| AUX error delta T | 1 to 30C (setup menu) |
Applies to: Versatronik 300 AUX output in external heat mode
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 300 Cascade Control manual, p. 30. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.