Viessmann · Boiler · Heating

AUX output as heat demand

Versatronik 300

What happens, in order

  1. Turn on AUX when all non-faulted, non-ECO lock boilers are running and set point still cannot be met.
  2. AUX turns on when common supply temperature drops below set point by the differential, and stays below it for the configured time.
  3. Once on, AUX stays on for the minimum run time.
  4. AUX turns off when the common supply temperature is satisfied, or when either non-faulted, non-ECO lock boiler stages off.

Timings and thresholds

ItemValue
AUX minimum run time1 to 99 min (setup menu)
AUX error delta T1 to 30C (setup menu)

Applies to: Versatronik 300 AUX output in external heat mode

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 300 Cascade Control manual, p. 30. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.