Trane · Heat pump · Heating
Unrestricted mode heating (heat pump with furnace backup)
What happens, in order
- If the heat pump alone can meet the building load, it runs to hold the setpoint regardless of outdoor temperature.
- If the heat pump cannot meet the load, the control turns the heat pump off and runs the furnace.
- The furnace may run continuously or cycle as needed.
- The control returns to heat pump operation when the building load drops to a low level.
- Emergency Heat mode forces furnace-only operation.
Applies to: Heat pump with fossil fuel auxiliary heat
Models
More Trane heat pump sequences
- Fan check · Startup
- Dual fuel transition from furnace to heat pump · Heating
- Emergency heat (EM) sequence, heat pump only · Heating
- Emergency heat sequence · Heating
- Heat pump heating sequence · Heating
- Heat pump heating sequence and aux stage · Heating
- Heat pump low-temperature fallback to aux · Heating
- Heat pump warm air discharge · Heating
Related
Trane error codes · Trane tips · Trane parts · All Trane sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: 18-HD29D3-4 installer's guide, p. 17. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.