Trane · Heat pump · Heating

Emergency heat sequence

XR103TCONT103

What happens, in order

  1. Set the SYSTEM switch to EMER. EMER flashes.
  2. Set the setpoint above room temperature. Auxiliary heat starts and the flame icon flashes.
  3. Set the setpoint below room temperature. Auxiliary heat stops.

Codes you may see during this

EMER

Applies to: Heat pump with auxiliary heat on terminal E

Models

TCONT103XR103

More Trane heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane TCONT103 installation and user guide, p. 9. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.