Trane · Heat pump · Heating

Restricted mode heating (heat pump first, furnace above balance point limit)

XR402

What happens, in order

  1. Above the Heat Pump Restricted Mode outdoor temperature, the control tries the heat pump first.
  2. If the heat pump cannot meet the load, the control switches to the furnace and turns the heat pump off.
  3. The furnace may run continuously or cycle as needed.
  4. Below the ISU step 43 outdoor temperature, only the furnace runs and the heat pump stays off.
  5. When outdoor temperature rises above the Resume Heat Pump Operation temperature (ISU step 44) and the building load is low, heat pump operation resumes.
  6. Emergency Heat mode forces furnace-only operation.

Timings and thresholds

ItemValue
Outdoor temperature comparison intervalEvery 10 minutes
Resume outdoor temperature minimum distance above Restricted Mode temperature4 degrees

Applies to: Heat pump with fossil fuel auxiliary heat and outdoor sensor

Models

TCONT402AN32DA

More Trane heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: 18-HD29D3-4 installer's guide, p. 17. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.