Trane · Heat pump · Heating

Dual fuel transition from furnace to heat pump

XR402

What happens, in order

  1. Furnace runs for heat as needed.
  2. When the furnace turns off, the control waits for the minimum time delay before the heat pump can start.
  3. The heat pump turns on after the delay ends.
  4. No external dual fuel kit is required with this control.

Timings and thresholds

ItemValue
Minimum comfort control delay between furnace off and heat pump on45 seconds

Applies to: Dual fuel heat pump with fossil fuel auxiliary heat

Models

TCONT402AN32DA

More Trane heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: 18-HD29D3-4 installer's guide, p. 17. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.