Dual fuel transition from furnace to heat pump
What happens, in order
- Furnace runs for heat as needed.
- When the furnace turns off, the control waits for the minimum time delay before the heat pump can start.
- The heat pump turns on after the delay ends.
- No external dual fuel kit is required with this control.
Timings and thresholds
| Item | Value |
|---|---|
| Minimum comfort control delay between furnace off and heat pump on | 45 seconds |
Applies to: Dual fuel heat pump with fossil fuel auxiliary heat
Models
More Trane heat pump sequences
- Fan check · Startup
- Emergency heat (EM) sequence, heat pump only · Heating
- Emergency heat sequence · Heating
- Heat pump heating sequence · Heating
- Heat pump heating sequence and aux stage · Heating
- Heat pump low-temperature fallback to aux · Heating
- Heat pump warm air discharge · Heating
- Restricted mode heating (heat pump first, furnace above balance point limit) · Heating
Related
Trane error codes · Trane tips · Trane parts · All Trane sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: 18-HD29D3-4 installer's guide, p. 17. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.