Trane · Heat pump · Heating
Heat pump low-temperature fallback to aux
What happens, in order
- If indoor temperature drops below 45°F from a heat pump fault, the heat pump turns off and aux heat is used.
- 'Call for Service' shows on the display.
- Press any key to retry the heat pump and clear the call-for-service icon.
- Or when setpoint is reached on aux, the heat pump resumes on the next call for heat.
Codes you may see during this
Call for Service
Applies to: HP1/HP2 with aux heat
Models
More Trane heat pump sequences
- Fan check · Startup
- Dual fuel transition from furnace to heat pump · Heating
- Emergency heat (EM) sequence, heat pump only · Heating
- Emergency heat sequence · Heating
- Heat pump heating sequence · Heating
- Heat pump heating sequence and aux stage · Heating
- Heat pump warm air discharge · Heating
- Restricted mode heating (heat pump first, furnace above balance point limit) · Heating
Related
Trane error codes · Trane tips · Trane parts · All Trane sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Trane XR302/XR303 installation and user guide, p. 18. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.