Trane · technician tips
Trane service menus, test modes and resets
201 tips for air handler, furnace, general, heat pump: access codes, button combinations, test modes and the resets you need at the appliance.
Jump to: Access & passwords (18) · Button combinations (8) · Service & test modes (15) · Reset & cancel (23) · Settings shortcuts (33) · Commissioning (39) · Other (65)
Access & passwords
Installer and service menu codes, and how to get into them.
Blower door interlock
Furnace · UH1 / DH1
The blower door switch cuts power to the blower and gas valve when the door is removed.
- Disconnect power before removing the blower door.
- Keep all panels closed during operation to avoid fume escape.
Applies to: Furnace service access
Source: Trane 18-CD29D1-11 installer's guide, p. 36. Written in our own words; check the manual for your exact model.
Disable screen lock or guest access
General · ComfortLink II XL1050
Turn off either feature from its own screen.
- Temporarily unlock the feature and go to its screen.
- Select OFF to disable Guest Access or Screen Lock.
Applies to: XL1050 screen lock and guest access
Source: Trane ComfortLink II XL1050 user guide 32-5093-04B-EN, p. 25. Written in our own words; check the manual for your exact model.
Enable screen lock and guest access
General · ComfortLink II XL1050
Locks the screen against user changes. Guest access still allows small setpoint changes.
- Select MENU > SETTINGS > SCREEN > SCREEN LOCK.
- Select ON to enable Screen Lock.
- Select ON to enable Guest Access, if wanted.
Applies to: XL1050 screen lock
Source: Trane ComfortLink II XL1050 user guide 32-5093-04B-EN, p. 25. Written in our own words; check the manual for your exact model.
Guest access and screen lock behaviour
General · ComfortLink II XL1050
Guest access lets users change setpoints by up to 5 degrees; other settings stay locked. Screen lock engages after 1 minute of inactivity.
- Hold the Menu button for 5 seconds to temporarily unlock a locked screen.
Applies to: XL1050 screen lock and guest access
Source: Trane ComfortLink II XL1050 user guide 32-5093-04B-EN, p. 25. Written in our own words; check the manual for your exact model.
Keypad lockout
General · XR302, XR303, TCONT302, TCONT303
Keypad lockout is set in configuration screen 26. The display shows a keypad lock icon when locked.
- Open the installer menu and go to screen 26.
- Choose L (total) to lock all keys, P (partial), or Temperature Limit for a limited range.
- To unlock, press the menu key (the key disappears) and hold for 20 seconds.
Applies to: TCONT302 / TCONT303
Source: TCONT302 and 303 installation and user guide, p. 13, 14, 24. Written in our own words; check the manual for your exact model.
Open the custom schedule screen
General · ComfortLink XL850
Schedules are edited from the Custom Schedule screen. The same screen is also reached with SHOW SCHEDULES on the Temperature Control Panel.
- Select Home Screen > Menu > Schedules & Presets > Custom Schedule.
- Or select SHOW SCHEDULES from the Temperature Control Panel.
Applies to: XL850 Smart Control
Source: ComfortLink Trane XL850 Smart Control User Guide (032-5091-06C-EN), p. 12 and 15. Written in our own words; check the manual for your exact model.
Open the User Setup Wizard
General · ComfortLink XL850
The wizard covers the user-configurable settings. Once it has started it cannot be cancelled, so finish it in one pass.
- Select MENU > SETTINGS > USER SETUP WIZARD.
Applies to: XL850 Smart Control
Source: Trane XL850 Smart Control user guide 032-5091-06C-EN, p. 3. Written in our own words; check the manual for your exact model.
Set access restrictions
General · ComfortLink XL850
Limits what users can change on the control.
- Go to Home Screen > Menu > Settings > Screen > Access Restrictions.
Applies to: XL850 Smart Control
Source: Trane XL850 Smart Control user guide, p. 20. Written in our own words; check the manual for your exact model.
Unlock a forgotten keypad lockout
General · XR302, XR303
If the lockout code is forgotten, the keypad can be unlocked without it.
- Press the menu key (the key will disappear).
- Hold it for 20 seconds.
- The thermostat unlocks.
Applies to: TCONT302 / TCONT303 keypad lockout
Source: Trane XR302/XR303 installation and user guide, p. 24. Written in our own words; check the manual for your exact model.
Unlock a keypad that has a lockout code
General · XR302, XR303
Use the code entered during keypad lockout setup.
- Press Menu, then press Installer Config.
- Display shows 000 and keypad lock.
- Enter the lockout combination and press the key.
Applies to: TCONT302 / TCONT303
Source: Trane XR302/XR303 installation and user guide, p. 17. Written in our own words; check the manual for your exact model.
Enter installer setup
Heat pump · XR402
Installer setup holds the installer options (steps 1 to 49). Set the control to OFF and the fan to AUTO before you enter it.
- Set System Mode to OFF.
- Set Fan to AUTO.
- Press and hold Mode and Up Arrow together until SET-UP shows on the display.
- Press Mode to move forward one step. Press Fan to go back one step.
- Use Up and Down arrows to view or change each option.
Applies to: TCONT402AN32DA Comfort Control
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 3. Written in our own words; check the manual for your exact model.
Enter user setup
Heat pump · XR402
User setup holds the owner options (steps 50 to 62).
- Press and hold Mode and Fan together.
Applies to: TCONT402AN32DA Comfort Control
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 3. Written in our own words; check the manual for your exact model.
Keypad lock on and off
Heat pump · XR402
The keypad can be locked so the settings cannot be changed by accident. The LCD shows Keypad Locked when the lock is on.
- Press the UP and DOWN arrow keys together and hold for 2 seconds to lock the keypad.
- Repeat the same key combination to unlock the keypad. The Keypad Locked message then clears.
Applies to: TCONT402AN32DA Comfort Control
Source: 18-HD29D3-4 installer's guide, p. 16. Written in our own words; check the manual for your exact model.
Button combinations
Key presses that open menus, show readouts or switch modes.
Display backlight ON/OFF
General · XR102
Backlight is off by default. When it is on, the light comes on for a short time after any button press.
- Set the SYSTEM switch to HEAT.
- Press both buttons together and hold for two seconds. The display alternates between the backlight label and FF.
- Press the up or down arrow to change FF to ON.
- Move the SYSTEM switch to OFF to exit the feature.
Applies to: All XR102 thermostats
Source: Trane XR102 installation and user guide, p. 10. Written in our own words; check the manual for your exact model.
Enable and disable keypad lockout
General · XR202, TCONT202
Keypad lockout disables the buttons to prevent unwanted changes. The lock icon shows when it is active. The button named in the manual for this step is not legible in the extract, so confirm the button on the unit.
- To turn lockout on, press and hold the indicated button together with Menu until the lock icon appears.
- To turn lockout off, press and hold the same buttons together with Menu for 3 seconds.
- Alternatively, set installer item 99 to On or OFF.
Applies to: Trane XR202 / TCONT202
Source: 18-HD51D1-1C-EN Installation and User Guide, p. 11. Written in our own words; check the manual for your exact model.
Switch between heat and cool in Auto mode
General · XR302, XR303
When Auto changeover picks the wrong mode.
- Press both the heat and cool keys at the same time to switch to the other mode.
Applies to: TCONT302 / TCONT303 Auto mode
Source: Trane XR302/XR303 installation and user guide, p. 20. Written in our own words; check the manual for your exact model.
Turn keypad lockout on or off
General · XR203
Locks the buttons to prevent changes. The lock icon shows when it is on.
- Press and hold the button shown in the manual (its name is missing from the page text) together with the Menu button until the lock icon appears to turn lockout on
- Press and hold the same button with Menu for 3 seconds to turn lockout off
Applies to: Trane XR203 thermostat
Source: Trane XR203 installation and user guide, p. 17. Written in our own words; check the manual for your exact model.
Defeat equipment time delay for the current cycle
Heat pump · XR402
Skips the minimum on or off time delay for the current cycle only. The delay returns for the next cycle.
- Press Mode and Down Arrow together.
Applies to: TCONT402AN32DA Comfort Control
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 4. Written in our own words; check the manual for your exact model.
Lock and unlock the keypad
Heat pump · XR402
Locking stops changes to the thermostat settings by the homeowner. The display shows Keypad Locked when the lock is on.
- Press UP and DOWN arrows together and hold for 2 seconds to lock.
- Repeat the same press to unlock. The Keypad Locked message then disappears.
- If a setpoint will not change, check whether Keypad Locked is showing.
Applies to: XR402 Comfort Control
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 14, 16. Written in our own words; check the manual for your exact model.
Lock or unlock the keypad
Heat pump · XR402
Locks the keypad so the setpoints and modes cannot be changed. The LCD shows Keypad Locked when locked.
- Press and hold Up Arrow and Down Arrow together to lock or unlock the keypad.
Applies to: TCONT402AN32DA Comfort Control
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 4. Written in our own words; check the manual for your exact model.
Override the minimum off time for the current cycle
Heat pump · XR402
Minimum off time delays can be skipped for the current cycle only. The next cycle enforces them again.
- Press Mode and Down arrow together and hold for about 2 seconds.
- If the system still does not start, lower the cooling setpoint or raise the heating setpoint below or above room temperature.
Applies to: XR402 Comfort Control
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 16. Written in our own words; check the manual for your exact model.
Service & test modes
Forced fan, low and high fire, test and diagnostic modes, error history and live data.
Run test mode (furnace)
Air handler · Trane P0V0
Lets the technician watch the blower perform its stages without starting the outdoor unit. Option holds (HLD) a step. The blower takes roughly 70 seconds to start the test.
- Press Menu until run appears, then press Option; the display flashes three times and the test begins
- Blower runs at 1st-stage compressor speed 30 s, then 2nd-stage speed 30 s; the pair repeats two more times
- Exit with a short press of Menu, by cycling blower power, or by making a valid call for capacity or fan
Applies to: P0V0 modular blower integrated control (IMBC)
Source: Trane P0V0 modular blower installer's guide 18-GE20D1-1E-EN, Integrated Modular Blower Control Menu, p.29-30. Written in our own words; check the manual for your exact model.
Carbon monoxide spillage test (vent check)
Furnace · UH1 / DH1
Run before returning a furnace to service on a shared vent. Failure to follow this can cause carbon monoxide poisoning or death.
- Seal any unused openings in the venting system.
- Check the venting system for proper size, horizontal pitch, blockage, restriction, leakage and corrosion, per NFPA 54 / CSA B149.1.
- Close building doors and windows and the doors between the space and the other appliances.
- Close fireplace dampers.
- Turn on clothes dryers and any appliance not on the vent. Run exhaust fans such as range hoods and bathroom exhausts at maximum speed. Do not run a summer exhaust fan.
- Light the appliance under test and set the thermostat so it runs continuously.
- After 5 minutes of main burner operation, test for spillage at the draft hood relief opening with a match or candle.
- If spillage shows, correct the venting to code before continuing.
- Return doors, windows, fans, dampers and other appliances to their previous condition.
Applies to: Draft hood appliances on a shared vent
Source: Trane AUH1B080A9421B installer's manual, p. 18. Written in our own words; check the manual for your exact model.
Run test mode (furnace)
Furnace · Trane S8V2, Trane S8B1, Trane S8X1, Trane S8X2
Lets the technician watch the inducer, igniter and blower step through stages without firing the burner or running the outdoor unit. Option holds a step (HLd). The test takes a short while to begin.
- Press Menu until run appears, then press Option; the display flashes three times and the test starts
- Steps: inducer 1st then 2nd stage (30 s each), igniter 10 s, then blower at 1st/2nd-stage compressor speed and 1st/2nd-stage gas heat speed (10 s each); the sequence repeats two more times
- Exit by pressing Menu briefly, cycling furnace power, or making a valid thermostat call
Applies to: S8V2, S8B1, S8X1, S8X2
Source: Trane S8V2 installation FNR-SVX003A-EN, Run Test Mode, p.57-58; Trane S8B1/S8X1/S8X2 installation 18-CE14D1-1A-EN, Display Codes, p.58. Written in our own words; check the manual for your exact model.
Cool call test (diagnostic click)
General · XR302, XR303
Same test as heat but for cooling.
- Set SYSTEM switch to COOL.
- Lower the setpoint below room temperature.
- Wait up to 5 minutes for the click.
- If no click after reset, replace thermostat.
Applies to: TCONT302 / TCONT303 cooling
Source: Trane XR302/XR303 installation and user guide, p. 24. Written in our own words; check the manual for your exact model.
Fan test
General · XR203
Checks the blower from the thermostat. Needs a G terminal connection. Without G, skip to the heating test.
- Turn on power to the system.
- Press the fan button to select On. The blower should start.
- Press the fan button to select Auto. The blower should stop immediately.
- If Circulation Fan is in use, FAn shows on the home screen and the fan runs for its set percentage of time.
Applies to: XR203 thermostat
Source: Trane XR203 installation and user guide, p. 15. Written in our own words; check the manual for your exact model.
Heat call click test
General · XR102
A soft click from the thermostat when heat is called usually means the thermostat is working. No click points to the thermostat or its wiring.
- Set the SYSTEM switch to HEAT.
- Raise the setpoint above room temperature.
- Listen for a soft click within a few seconds.
- If there is no click, do the reset and check again. If there is still no click, replace the thermostat.
- If it clicks but there is no heat, check the furnace or have a service person verify heating.
Applies to: Heating systems
Source: Trane XR102 installation and user guide, p. 11. Written in our own words; check the manual for your exact model.
Heat call test (diagnostic click)
General · XR302, XR303
Confirms the thermostat relay operates before blaming the furnace.
- Set SYSTEM switch to HEAT.
- Raise the setpoint above room temperature.
- Listen for a soft click within a few seconds.
- If no click, reset the thermostat and retest.
- If it clicks, the furnace or service technician must check heat operation.
Applies to: TCONT302 / TCONT303 heating
Source: Trane XR302/XR303 installation and user guide, p. 24. Written in our own words; check the manual for your exact model.
Check humidifier output
Heat pump · XR303
Tests the humidifier call while the heating system is running.
- With System On showing and heat running, press HUMIDITY once.
- Raise the humidity setpoint 2% or more above room humidity.
- Hum On shows when the humidifier is called.
Applies to: TCONT303 humidifier
Source: Trane XR302/XR303 installation and user guide, p. 19. Written in our own words; check the manual for your exact model.
Enter manual test mode
Heat pump · XR402
Manual test mode energizes each load output one step at a time so you can check the wiring and equipment. The mode times out and returns to normal operation 4 minutes after the last key press.
- Set System Mode to OFF.
- Set Fan to AUTO.
- Press and hold Mode and Down Arrow together.
- Advance through the steps with Mode or Fan and change outputs with Up or Down.
- Energize the G fan relay (step 70) before you energize the Y compressor step (step 72) so the fan runs with the compressor.
- Press and hold Mode to move to step 80, then press $ to exit.
Applies to: TCONT402AN32DA Comfort Control
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 4. Written in our own words; check the manual for your exact model.
Force a dehumidification cycle
Heat pump · XR303
Forces dehumidification equipment to run for one cooling cycle when room humidity is already below the adjustment range.
- Press HUMIDITY when System On shows and cooling runs.
- Press the down key and hold it at 40% for 4 seconds.
- DeHum On forces one full cooling cycle.
Applies to: TCONT303 cooling dehumidification
Source: Trane XR302/XR303 installation and user guide, p. 19. Written in our own words; check the manual for your exact model.
Manual test mode
Heat pump · XR402
Manual test mode lets the servicer switch each control output on in turn. The step list (Table 1, steps 70-78) is not on these pages.
- Set System Mode to OFF.
- Set Fan to AUTO.
- Press and hold Mode and Down arrow together for 2 seconds.
- Work through the test steps, using Mode and Fan to move between them.
- Use the step list in Table 1 (steps 70-78) for what each step energizes.
Applies to: XR402 Comfort Control
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 16. Written in our own words; check the manual for your exact model.
Manual Test Mode entry
Heat pump · XR402
Manual Test Mode lets the servicer switch each control output on and off to check the wiring and equipment. The test step list is in Table 1, steps 70-78, which is not on these pages.
- Set the system Mode to OFF.
- Set the Fan to AUTO.
- Press the MODE and DOWN arrow keys together and hold for 2 seconds.
- Step through the test outputs using the Mode and Fan keys, using Table 1 steps 70-78 for the test details.
Applies to: TCONT402AN32DA Comfort Control
Source: 18-HD29D3-4 installer's guide, p. 16. Written in our own words; check the manual for your exact model.
Force a defrost cycle with the button
Heat pump · Trane 5TWR7
Holding the forced defrost button on the control board starts a defrost; the display then shows 7 as the first digit (Defrosting). Not possible in cooling.
- Run the unit in heating mode with the thermostat calling
- Hold the forced defrost button on the control board down for over 5 seconds
- The display shows 7 as the first digit when forced defrost begins
Applies to: 5TWR7 multi-speed outdoor drive
Source: Trane 5TTR7/5TWR7 installation ODR-SVN002E-EN, Forced Defrost, p.34. Written in our own words; check the manual for your exact model.
Reset & cancel
Clearing lockouts, service reminders and fault history; skipping purge or de-air programs.
Reset the control to factory defaults
Air handler · Trane P0V0
Holding Menu and Option together at idle resets all menu values to factory defaults; the display flashes FD three times to confirm.
- Make sure the display is in idle (IdL)
- Hold Menu and Option together for 15 seconds, then release
- FD flashes three times
Applies to: P0V0 modular blower integrated control (IMBC)
Source: Trane P0V0 modular blower installer's guide 18-GE20D1-1E-EN, Fault Code Recovery, Resetting Factory Defaults, p.31. Written in our own words; check the manual for your exact model.
Burner box temperature limit reset
Furnace · UH1 / DH1
A manual reset temperature limit is on the burner box and opens the gas circuit on overheat.
- If the limit trips, find and correct the overheat cause.
- Reset the manual limit on the burner box.
- For full shutdown, set the main gas valve switch to OFF and disconnect electrical supply.
Applies to: All models
Source: Trane 18-CD29D1-11 installer's guide, p. 36. Written in our own words; check the manual for your exact model.
Burner box temperature limit shutdown
Furnace · AUH1B
The manual reset limit on the burner box opens and shuts off gas flow when temperature is excessive.
- Check vent and combustion air inlet terminations for blockage.
- Clear any blockage, then press the reset button.
- If there is no blockage, have a qualified servicer reset the limit.
Applies to: AUH1B furnaces
Source: Trane installer's manual (AUH1B040A9241A), p. 40-41. Written in our own words; check the manual for your exact model.
Clear a lockout condition
Furnace · Gas Heating Systems
A lockout condition can be cleared by cycling the power.
- Turn power on-off-on-off twice within 30 seconds.
Applies to: Gas heating system in lockout
Source: Trane gas heating system owner's information 32-5083-1C-EN, p. 3. Written in our own words; check the manual for your exact model.
Reset after lockout
Furnace · AUH1B
The control stays locked out until it is reset manually.
- Turn system power off, on, off, then on again within 30 seconds.
- Reset can be done at the unit power source or at the thermostat.
- If the sequence is not completed within 30 seconds, it will not reset.
Applies to: AUH1B furnaces
Source: Trane installer's manual (AUH1B040A9241A), p. 41. Written in our own words; check the manual for your exact model.
Reset the control to factory defaults
Furnace · Trane S8V2, Trane S8B1, Trane S8X1, Trane S8X2
Holding Menu and Option together at idle resets all menu values to factory defaults; the display flashes FD three times to confirm.
- Make sure the display is in idle (IdL)
- Hold Menu and Option together for 15 seconds, then release
- FD flashes three times
Applies to: S8V2, S8B1, S8X1, S8X2
Source: Trane S8V2 installation FNR-SVX003A-EN, Resetting Factory Defaults, p.60; Trane S8B1/S8X1/S8X2 installation 18-CE14D1-1A-EN, p.59. Written in our own words; check the manual for your exact model.
Advanced Z-Wave functions: caution
General · ComfortLink II XL1050
Learn, Unregister and Factory Reset are high-impact. Factory reset removes all devices. If the bridge is the primary controller, all network devices are removed and must be re-added. Reset a secondary bridge only if its primary controller is missing or inoperable.
- Navigate to Home Screen > Menu > Smart Home > Advanced.
- Use Learn only to add the bridge to an existing network after putting the primary controller into Add Mode.
- Use Unregister to remove the bridge from Trane Home, which disables remote control.
- Use Factory Reset only when needed, then remove and re-add all devices.
Applies to: XL1050 Z-Wave bridge
Source: Trane ComfortLink II XL1050 user guide 32-5093-04B-EN, p. 29. Written in our own words; check the manual for your exact model.
Advanced Z-Wave functions: Learn, Unregister and Factory Reset
General · ComfortLink XL850
The Advanced Z-Wave screen has three powerful functions that should be used with caution. Navigate there from Home Screen > Menu > Smart Home > Advanced.
- Learn: to join an existing network, first put the primary controller into add mode, then press Learn on the bridge. This is not allowed if the bridge is a primary controller that already has Z-Wave devices.
- Unregister: removes the bridge from Trane Home and disables all remote control features.
- Factory Reset: clears all Z-Wave information and removes every device from the bridge. If this bridge is the primary controller, all devices in the network are removed and must be removed and re-added afterward.
- If the bridge is a secondary or inclusion controller, only reset it when the primary controller is missing or inoperable.
Applies to: XL850 bridge Z-Wave network
Source: ComfortLink Trane XL850 Smart Control user guide (032-5091-06C-EN), p. 28. Written in our own words; check the manual for your exact model.
Cancel a permanent hold
General · XR203
A permanent hold bypasses the schedule until it is cancelled.
- Press Hold/Run again to return to the programmed schedule
Applies to: Trane XR203 thermostat
Source: Trane XR203 installation and user guide, p. 16-17. Written in our own words; check the manual for your exact model.
Cancel a temporary override or hold
General · XR302, XR303
Returns control to the program.
- Press Run Schedule to cancel a temporary override and return to the program.
- To resume after a permanent hold, press Run Schedule.
Applies to: TCONT302 / TCONT303
Source: Trane XR302/XR303 installation and user guide, p. 20. Written in our own words; check the manual for your exact model.
Cancel hold and return to schedule
General · XR203
The Hold button sets or cancels a permanent hold. The Hold/Run button returns to the home screen.
- Press Hold again to cancel a permanent hold and return to the programmed schedule.
- Press Hold/Run to exit to the home screen.
Applies to: XR203 thermostat
Source: Trane XR203 installation and user guide, p. 16. Written in our own words; check the manual for your exact model.
Reset schedule and user settings to factory defaults
General · XR202, TCONT202
Resets only the schedule and user settings. Installer settings are not listed as reset by this step.
- Press the Menu and Backlight buttons at the same time.
- Hold until the display goes blank and resets.
Applies to: Trane XR202 / TCONT202
Source: 18-HD51D1-1C-EN Installation and User Guide, p. 12. Written in our own words; check the manual for your exact model.
Reset the thermostat by removing batteries
General · XR202, TCONT202
Use this when the batteries are good but the display is blank or the keys do not respond. Menu settings and program are kept.
- Remove the batteries for 2 minutes.
- Reinstall the batteries.
- If the problem continues, replace the thermostat.
Applies to: Trane XR202 / TCONT202
Source: 18-HD51D1-1C-EN Installation and User Guide, p. 12. Written in our own words; check the manual for your exact model.
Reset thermostat (also restores factory defaults)
General · XR102
Use this after a voltage spike or static discharge blanks the display or causes erratic operation. The reset also restores factory defaults.
- Press both arrow buttons at the same time.
- While holding them, move the SYSTEM switch from OFF to HEAT.
- If the thermostat still does not work correctly after the reset, contact the heating/cooling service person or place of purchase.
Applies to: All XR102 thermostats
Source: Trane XR102 installation and user guide, p. 11. Written in our own words; check the manual for your exact model.
Reset thermostat after a voltage spike or static discharge
General · XR302, XR303
Use when the display is blank, the keypad does not respond, or operation is erratic.
- Remove the thermostat from the wall plate.
- Remove the batteries and wait 2 minutes.
- Replace the batteries and reattach the thermostat to the wall plate.
- If it still does not work, contact the heating/cooling service person or place of purchase.
Applies to: TCONT302 / TCONT303
Source: Trane XR302/XR303 installation and user guide, p. 24. Written in our own words; check the manual for your exact model.
Reset thermostat by removing batteries
General · XR203
Use when the display is blank or the buttons do not respond while the batteries are good. Menu settings and the program are kept.
- Remove the batteries for 2 minutes
- Reinstall the batteries
- If the problem continues after reinstalling, replace the thermostat
Applies to: Trane XR203 thermostat
Source: Trane XR203 installation and user guide, p. 18. Written in our own words; check the manual for your exact model.
Restore factory default settings
General · XR302, XR303, TCONT302, TCONT303
Resets the program, clock and configuration menu to factory defaults.
- Press the key named in the manual (key name not legible in extracted text) together with the SYSTEM key at the same time.
- Wait while the display goes blank for a few seconds, then shows all segments briefly.
- Reset the configuration options and program again after the reset.
Applies to: TCONT302 / TCONT303
Source: TCONT302 and 303 installation and user guide, p. 14. Written in our own words; check the manual for your exact model.
Exit setup options at step 99 (save, cancel, clear, factory reset)
Heat pump · XR402
Step 99 is the exit point of both setup menus. SA saves all settings. CA cancels changes. CL clears history and service counts only. CS clears installer and user setups back to their defaults. FA resets everything to factory and also clears history. US restores only the user defaults and does not touch installer settings.
- Advance with Mode or the Energy Saving key until step 99 shows.
- Pick SA, CA, CL, CS, FA or US with the arrow keys.
- Press Mode to confirm and exit.
- Wait at least 5 seconds after saving before removing power so the settings write to memory.
Applies to: XR402 Comfort Control setup
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 12-13. Written in our own words; check the manual for your exact model.
Filter reminder reset and timer access
Heat pump · XR402
The FILTER indicator flashes when the preset filter time runs out. Resetting the timer clears the flashing. Pressing the Filter/OD key once after a reset shows the days left until the next change.
- Press the Filter/OD key to reset the filter timer after changing the filter.
- Press Filter/OD again to show the days remaining until the next filter change.
- Press and hold Filter/OD to enter quick setup for the filter timer value.
Applies to: TCONT402AN32DA Comfort Control
Source: 18-HD29D3-4 installer's guide, p. 16. Written in our own words; check the manual for your exact model.
Minimum off time delay override
Heat pump · XR402
The minimum off time delay can be skipped for the current cycle. The delay is enforced again on the next cycle. It may be necessary to change the setpoint to start the system.
- Press the Mode and DOWN arrow keys together and hold for about 2 seconds.
- If the system does not start, lower the cooling setpoint or raise the heating setpoint to call for operation.
Applies to: TCONT402AN32DA Comfort Control
Source: 18-HD29D3-4 installer's guide, p. 16. Written in our own words; check the manual for your exact model.
Power loss during setup can erase entries
Heat pump · XR402
Selections are only safe once the control has had 5 seconds to write them. A power loss before that can lose the entries.
- After saving, wait at least 5 seconds before cutting power.
- If SERVICE flashes after a power interruption, press any key.
- Check and re-enter the setup choices.
Applies to: XR402 Comfort Control
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 3. Written in our own words; check the manual for your exact model.
Reset the thermostat
Heat pump · XR103, TCONT103
Resets the thermostat after a voltage spike or static discharge blanks the display or causes erratic operation. This also restores factory defaults.
- Press the two keys named in the reset instruction together (the key names are not legible in this extraction).
- Hold them while switching the SYSTEM switch from OFF to HEAT.
- If the thermostat still does not work after reset, contact the service person or place of purchase.
Applies to: XR103 / TCONT103
Source: Trane TCONT103 installation and user guide, p. 10. Written in our own words; check the manual for your exact model.
Restore factory default settings
Heat pump · XR402
The control can be returned to its factory defaults from the configuration menu. The menu step is Table 3, step 99, which is not on these pages.
- Enter the installer configuration menu.
- Go to step 99 in Table 3 and select the factory default restore.
- Re-enter the site settings after the reset.
Applies to: TCONT402AN32DA Comfort Control
Source: 18-HD29D3-4 installer's guide, p. 16. Written in our own words; check the manual for your exact model.
Settings shortcuts
Where the useful parameters live and what they are set to from the factory.
Heat anticipator setting
Furnace · UH1 / DH1
Set the room thermostat heat anticipator to match the current measured.
- Measure the control current flow.
- Set the thermostat heat anticipator to that value, or to the value in the wiring diagram notes (found in Service Facts or inside the furnace casing).
Applies to: Room air thermostat
Source: Trane 18-CD29D1-11 installer's guide, p. 36. Written in our own words; check the manual for your exact model.
Indoor fan setting in humid conditions
Furnace · Gas Heating Systems
When indoor humidity is above 60% RH or feels uncomfortably humid, run the indoor fan in AUTO only.
- Set the fan to AUTO at the thermostat.
Applies to: Gas heating system with thermostat fan control
Source: Trane gas heating system owner's information 32-5083-1C-EN, p. 2. Written in our own words; check the manual for your exact model.
Add up to three home screen widgets
General · ComfortLink II XL1050
Up to three of the seven available widgets can be shown on the home screen.
- Go to Menu > Settings > Screen > Screen Layout.
- Select up to three widgets.
- Select Apply.
Applies to: XL1050 home screen
Source: 32-5093-04B-EN XL1050 user guide, p. 10, p. 13. Written in our own words; check the manual for your exact model.
Add widgets to the home screen
General · ComfortLink XL850
Up to two widgets can appear on the home screen.
- Go to Menu > Settings > Screen > Screen Layout.
- Choose up to two widgets.
Applies to: XL850 Smart Control
Source: Trane XL850 Smart Control user guide 032-5091-06C-EN, p. 3, p. 4, p. 8. Written in our own words; check the manual for your exact model.
Auto Schedule (fast heat or cool setback)
General · XR302, XR303
Sets all daytime heat periods to one comfort temperature with a 6° night setback. Cool auto schedule sets all cool periods to one temperature.
- Available after first power-up, after a reset, or after AS is turned on in the configuration menu.
- In Heat mode, press Auto Schedule once.
- Set the comfort temperature with up/down keys.
- Press Auto Schedule again to program the schedule.
Applies to: TCONT302 / TCONT303
Source: Trane XR302/XR303 installation and user guide, p. 21. Written in our own words; check the manual for your exact model.
Choose Home screen widgets
General · ComfortLink XL850
Up to two widgets can be shown on the Home screen.
- Go to Menu > Settings > Screen > Screen Layout.
- Select up to two widgets (or apps).
- Select Apply.
Applies to: XL850 Smart Control
Source: ComfortLink Trane XL850 Smart Control User Guide (032-5091-06C-EN), p. 8-9. Written in our own words; check the manual for your exact model.
Circulation fan minimum run time
General · XR203
Sets the minimum percentage of each day the fan runs, counting time already run for heating or cooling.
- Set User Menu item 04 (Fn) from OFF to 10 to 100 percent
- Example: a 30 percent setting makes sure the fan runs at least 30 percent of the day
Applies to: Trane XR203 thermostat
Source: Trane XR203 installation and user guide, p. 17. Written in our own words; check the manual for your exact model.
Confirm scheduling is enabled
General · ComfortLink XL850
A schedule only runs if scheduling is turned on. Check this before defining periods.
- Go to MENU > SCHEDULES & PRESETS.
- Check that USE SCHEDULES is set to ON.
Applies to: XL850 Smart Control
Source: ComfortLink Trane XL850 Smart Control User Guide (032-5091-06C-EN), p. 15. Written in our own words; check the manual for your exact model.
Copy a program from one day to another
General · XR302, XR303
Copies a day's schedule to other days.
- In Set Schedule, select the source day with Advance Day.
- Press Copy; the source day shows.
- Press Advance Day until the target day flashes; repeat for other days.
- Press Copy to finish, then Run Schedule.
Applies to: TCONT302 / TCONT303 7-day or 5+1+1 programming
Source: Trane XR302/XR303 installation and user guide, p. 20. Written in our own words; check the manual for your exact model.
Enable scheduling before editing a schedule
General · ComfortLink II XL1050
Scheduling is off until it is enabled. If it is off, a message shows instead of the weekly schedule.
- Go to MENU > SCHEDULES.
- Select ENABLE SCHEDULE.
- The factory default 7-day schedule then appears for editing.
Applies to: XL1050 control
Source: XL1050 User Guide (32-5093-04B-EN), p. 20. Written in our own words; check the manual for your exact model.
Enable, disable or manually trigger Smart Optimization
General · ComfortLink XL850
Smart Optimization can be turned off, turned on, or re-run from the menu.
- To disable, go to Home > Menu > Smart Optimization, select Disabled, then select Apply.
- To enable, go to Home > Menu > Smart Optimization, select Enabled, then select Apply. It runs in about 18 hours.
- To trigger it manually, disable the feature, then enable it again.
Applies to: XL850 Smart Control
Source: ComfortLink Trane XL850 Smart Control user guide (032-5091-06C-EN), p. 30. Written in our own words; check the manual for your exact model.
Enter heating or cooling program
General · XR302, XR303
Program heat or cool setpoints and times per period.
- Press Menu, then Set Schedule.
- Press SYSTEM to select Heat (or Cool).
- Set the period temperature with up/down keys.
- Set the start time with up/down keys (15-minute steps).
- Press Set Schedule to move to the next period; repeat for each day.
- Press Run Schedule when finished.
Applies to: TCONT302 / TCONT303
Source: Trane XR302/XR303 installation and user guide, p. 21. Written in our own words; check the manual for your exact model.
Hold a setpoint indefinitely with Permanent Hold
General · ComfortLink II XL1050
Permanent Hold keeps a manually set temperature until it is changed by hand. Pressing it again returns the control to the schedule.
- Adjust the setpoint to the wanted temperature.
- Press the Permanent Hold button. It shows ON and holds the setpoint.
- Press Permanent Hold again to turn it OFF and resume the schedule.
Applies to: XL1050 with scheduling enabled
Source: 32-5093-04B-EN XL1050 user guide, p. 10. Written in our own words; check the manual for your exact model.
Hold a temperature indefinitely
General · ComfortLink XL850
Use Permanent Hold to keep one setpoint until you change it by hand, instead of following the schedule.
- Adjust the setpoint to the wanted temperature.
- Select the Permanent Hold button so it shows ON.
- To end the hold, select Permanent Hold again so it shows OFF. The control then goes back to the schedule.
Applies to: XL850 Smart Control
Source: ComfortLink Trane XL850 Smart Control User Guide (032-5091-06C-EN), p. 8. Written in our own words; check the manual for your exact model.
Override a running schedule
General · ComfortLink XL850
With scheduling enabled, the Preset button is disabled and Permanent Hold is shown instead. The override lasts until the next period change.
- Adjust the temperature with the up and down arrows on the right of the Home screen.
- Leave it; the schedule resumes at the next period change.
Applies to: XL850 Smart Control
Source: ComfortLink Trane XL850 Smart Control User Guide (032-5091-06C-EN), p. 8. Written in our own words; check the manual for your exact model.
Permanent hold (bypass schedule)
General · XR203
Holds a set temperature with the system in Heat or Cool until hold is cancelled.
- With the System set to Heat or Cool, press Hold/Run momentarily
- Use the arrows to set the temperature
- Press Hold/Run again to return to the program
Applies to: Trane XR203 thermostat
Source: Trane XR203 installation and user guide, p. 17. Written in our own words; check the manual for your exact model.
Power stealing switch
General · XR302, XR303
The power stealing switch ships in the OFF position. ON can extend battery life but is not compatible with every furnace.
- Set the power stealing switch to ON only if battery life needs help.
- Cycle the furnace and confirm the inducer and/or indoor blower do not run continuously or without a call for heat.
- If they do run without a call, return the switch to OFF.
Applies to: TCONT302 / TCONT303
Source: 18-HD48D1-1C-EN installation and user guide, p. 4. Written in our own words; check the manual for your exact model.
Set 1-Touch Presets (Home, Away, Sleep)
General · ComfortLink XL850
Presets give fixed heating and cooling setpoints for Home, Away and Sleep. Scheduling must be off for all three presets. When scheduling is on, only the Away preset is available for energy savings. With scheduling off, setpoints hold until changed by hand.
- Turn scheduling off at Home > Menu > Schedules & Presets > Use Schedules Off, or use the touch icon on the Home Screen if scheduling is already off.
- Go to Home Screen > Menu > Schedules & Presets > 1-Touch Presets.
- Select the blue cooling setpoint and set it with Up/Down.
- Select the red heating setpoint and set it with Up/Down.
- Repeat for the Home and Sleep presets.
- Select Apply, then Home to return to the Home Screen.
Applies to: XL850 Smart Control, scheduling disabled
Source: Trane XL850 Smart Control user guide, p. 18-19. Written in our own words; check the manual for your exact model.
Set a permanent temperature hold
General · ComfortLink XL850
Holds one temperature indefinitely, ignoring the schedule until the hold is turned off.
- Adjust the set point to the desired temperature.
- Select the Permanent Hold button. It shows ON.
- To end the hold, select Permanent Hold again so it shows OFF. The control then goes back to the schedule.
Applies to: XL850 Smart Control
Source: Trane XL850 Smart Control user guide 032-5091-06C-EN, p. 8. Written in our own words; check the manual for your exact model.
Settings screen items
General · ComfortLink II XL1050
Settings covers date, time and time zone (not needed when connected to Trane Home), service reminders, temperature scale, deadband, calibration, outdoor temperature sensor source, screen brightness, backlight timer, screensaver and color theme, software upgrade, restart, and Wi-Fi/network setup including Advanced Setup, Network Properties and Diagnostics.
- Set date, time and time zone manually only if not connected to Trane Home.
- Set temperature scale and deadband as required.
- Choose the outdoor temperature sensor source for the display.
Applies to: XL1050 settings screen
Source: XL1050 user guide 32-5093-04B-EN, p. 7. Written in our own words; check the manual for your exact model.
Show and change heating and cooling set points
General · ComfortLink XL850
The temperature control panel is only shown on the Classic View home screen. It is used to set targets manually.
- On the Classic View home screen, select the heating or cooling set point to open the control panel.
- Use the up or down arrows to change the set point.
- Select Show Schedule to view or edit the schedule.
Applies to: XL850 Smart Control
Source: Trane XL850 Smart Control user guide 032-5091-06C-EN, p. 7. Written in our own words; check the manual for your exact model.
Switch between Simple and Classic home screen
General · ComfortLink XL850
Simple View is the default. Classic View adds the temperature control panel and the air cleaner mode button.
- From the home screen, go to Home Screen > Menu > Settings > Screen > Home View Options.
- Select Simple View or Classic View.
Applies to: XL850 Smart Control
Source: Trane XL850 Smart Control user guide 032-5091-06C-EN, p. 5. Written in our own words; check the manual for your exact model.
Temperature display adjustment (up to 3 degrees)
General · XR102
Use this to match the thermostat display to an existing thermometer. The adjustment range is plus or minus 3 degrees.
- Set the SYSTEM switch to OFF.
- Press both arrow buttons together and hold for two seconds.
- Press the up or down arrow until the display shows the wanted reading.
- Move the SYSTEM switch away from OFF to exit the feature.
Applies to: All XR102 thermostats
Source: Trane XR102 installation and user guide, p. 10. Written in our own words; check the manual for your exact model.
Temporarily override a running schedule
General · ComfortLink XL850
With scheduling enabled, the 1-Touch Preset button is disabled and Permanent Hold is shown. A manual change lasts only until the next period change.
- Adjust the temperature with the up or down arrows on the screen.
- The schedule resumes at the next period change.
- To change the schedule itself, use the schedule view and edit controls in the Temperature Control Panel. To keep current settings, disable the schedule.
Applies to: XL850 Smart Control
Source: Trane XL850 Smart Control user guide 032-5091-06C-EN, p. 7, p. 8. Written in our own words; check the manual for your exact model.
Temporary hold (program override)
General · XR203
Overrides the schedule until the next programmed period, with a minimum override of 2 hours.
- Press the up or down arrow until the desired temperature shows
- The thermostat returns to the program automatically after the override
Applies to: Trane XR203 thermostat
Source: Trane XR203 installation and user guide, p. 17. Written in our own words; check the manual for your exact model.
Use 1-Touch Presets with scheduling disabled
General · ComfortLink XL850
Presets Home, Away and Sleep are available only when scheduling is disabled. Their set points are configured in the setup wizard.
- Select Home, Away, Sleep or Off from the home screen preset buttons.
- To change preset targets, use the 1-Touch Presets setup in the wizard.
Applies to: XL850 Smart Control
Source: Trane XL850 Smart Control user guide 032-5091-06C-EN, p. 3, p. 7. Written in our own words; check the manual for your exact model.
Energy Savings key and offset quick access
Heat pump · XR402
The Energy Savings key toggles an offset that makes the heating setpoint cooler and the cooling setpoint warmer.
- Press the Energy Savings key ($) to turn the mode on, press again to turn it off.
- Press and hold the Energy Savings key to change the heating and cooling offsets directly.
Applies to: XR402 Comfort Control
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 16. Written in our own words; check the manual for your exact model.
Energy Savings mode toggle and offset access
Heat pump · XR402
Energy Savings lowers the heating setpoint and raises the cooling setpoint by an offset. Press the $ key to turn it on or off. Press and hold the $ key to go straight to the heating and cooling offset settings.
- Press the $ key to turn Energy Savings on or off.
- Press and hold the $ key to view or change the heating and cooling setpoint offsets.
Applies to: TCONT402AN32DA Comfort Control
Source: 18-HD29D3-4 installer's guide, p. 16. Written in our own words; check the manual for your exact model.
Filter reminder reset and check
Heat pump · XR402
The FILTER indicator flashes when the preset time has run out. The Filter/OD key resets and reads the filter timer.
- Press Filter/OD to reset the filter timer after changing the filter.
- Press Filter/OD again to see the days remaining.
- Press and hold Filter/OD to get into the filter timer setup.
Applies to: XR402 Comfort Control
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 16. Written in our own words; check the manual for your exact model.
Quick setup for continuous fan airflow
Heat pump · XR402
With BK output enabled, the continuous fan airflow can be changed from the front keypad without entering user setup.
- Press and hold the Fan key for a few seconds.
- Adjust continuous airflow between 35% and 100% in 5% steps.
Applies to: XR402 with BK output enabled
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 15. Written in our own words; check the manual for your exact model.
Commissioning
Start-up and set-up steps that are easy to miss.
Do not light burners manually
Furnace · UH1 / DH1
The control handles ignition automatically.
- Turn on the main electrical supply and set the thermostat above setpoint.
- The ignitor heats first, then the gas valve opens.
- After flame is proven, the flame control keeps the gas valve open until the thermostat is satisfied.
- Run the unit through one complete cycle at startup.
Applies to: Furnace startup
Source: Trane 18-CD29D1-11 installer's guide, p. 39. Written in our own words; check the manual for your exact model.
Downflow installation on combustible floors
Furnace · UH1, DH1
Do not set the furnace directly on carpet, tile or other combustible material except wood flooring.
- For a vertical downflow installation, use subbase BAYBASE-205 between the furnace and combustible flooring.
- A subbase is not required when a downflow furnace is installed vertically with a cased coil.
Applies to: Downflow furnaces
Source: Trane AUH1B080A9421B installer's manual, p. 7. Written in our own words; check the manual for your exact model.
Electrical connections and polarity
Furnace · UH1 / DH1
The integrated control is polarity sensitive.
- Connect the hot leg of the 120 V supply to the black power lead as shown on the wiring diagram.
- Provide a permanently live circuit with a separate circuit protection device.
- Ground the furnace per local code or the National Electrical Code.
- Electronic air cleaner and humidifier connections are provided on the integrated control.
Applies to: Furnace wiring
Source: Trane 18-CD29D1-11 installer's guide, p. 33. Written in our own words; check the manual for your exact model.
Location, access and clearance checks
Furnace · UH1, DH1
Confirm these before setting the furnace.
- Locate the furnace as close to the vent as practical and central to the heat distribution.
- Keep at least 24 inches of front access for service. Any access door must allow removal of the largest component.
- Keep at least 3 inches between the furnace front panel and any closed panel or door.
- Keep combustion and ventilation openings large enough and unobstructed. If outside air is used, set the openings at least 12 inches above the highest snow level.
- Leave enough supply plenum height above or below the furnace for a cooling coil if the coil is not yet installed.
- Install so electrical components are protected from water.
- Install the furnace level. Upflow units may tilt slightly left and/or forward; horizontal units may tilt slightly forward, for condensate drainage.
Applies to: All furnaces
Source: Trane AUH1B080A9421B installer's manual, p. 4. Written in our own words; check the manual for your exact model.
Minimum front and door clearances
Furnace · UH1/DH1
Front access and door clearance requirements for servicing.
- Confirm at least 24 in of front service access.
- Confirm at least 3 in between the furnace front panel and any closed panel or door.
Applies to: All UH1/DH1 furnaces
Source: Trane installer's guide 18-CD29D1-11, p. 8. Written in our own words; check the manual for your exact model.
Minimum return air temperature
Furnace · UH1/DH1
Return air must not fall below 55 F.
- Check return air temperature is at least 55 F before operating the furnace.
Applies to: UH1/DH1 furnaces
Source: Trane installer's guide 18-CD29D1-11, p. 9. Written in our own words; check the manual for your exact model.
Preliminary inspections before lighting
Furnace · UH1 / DH1
Check these items with gas and electrical power off.
- Confirm duct connections are sealed.
- Confirm filters are in place.
- Confirm venting is properly assembled.
- Confirm the blower door is in place.
- Set the gas valve switch to OFF, open the external gas valve, and purge air from the lines.
- Leak check all gas connections with soapy solution, then wait 5 minutes for any gas to clear. LP gas is heavier than air and may need forced ventilation.
- Set the gas valve switch to ON.
Applies to: Furnace startup
Source: Trane 18-CD29D1-11 installer's guide, p. 39. Written in our own words; check the manual for your exact model.
Prime the condensate trap at start-up
Furnace · AUH1B, UH1, DH1
The condensate trap must be filled before the first heating season.
- Prime the condensate trap during initial start-up, before heating season operation.
Applies to: Downward venting with condensate trap
Source: Trane installer's guide, p. 23. Written in our own words; check the manual for your exact model.
Residential garage installation
Furnace · UH1, DH1
A furnace in a residential garage needs extra protection.
- Mount the furnace so the burners and ignition source are at least 18 inches (46 cm) above the floor.
- Locate or protect the furnace from physical damage by vehicles.
Applies to: Furnaces in residential garages
Source: Trane AUH1B080A9421B installer's manual, p. 4. Written in our own words; check the manual for your exact model.
Set thermostat heat anticipator
Furnace · AUH1B
Set the heat anticipator to the measured current flow, or to the value listed in the notes on the wiring diagram.
- Measure the current flow, or find the value in the notes on the wiring diagram.
- Set the thermostat heat anticipator to that value.
Applies to: AUH1B furnaces
Source: Trane installer's manual (AUH1B040A9241A), p. 40. Written in our own words; check the manual for your exact model.
Upflow cased coil installation
Furnace · UH1, DH1
The cooling coil always sits downstream of the furnace airflow.
- Attach the cased coil with the supplied standoffs and drill screws.
- Insert each standoff into the cabinet alignment hole, run the drill screws through the standoffs, and screw them into the furnace top flange.
- Use the clearance alignment holes near the bottom of the coil wrapper.
Applies to: Upflow furnaces with cased coil
Source: Trane AUH1B080A9421B installer's manual, p. 7. Written in our own words; check the manual for your exact model.
Upflow return air openings for high-airflow models
Furnace · UH1, DH1
Applies to 5 or 6 ton upflow models where airflow exceeds 1800 CFM.
- Provide return air openings and filters on both sides, or on one side and the bottom, or on the bottom only.
Applies to: Upflow 5 or 6 ton models above 1800 CFM
Source: Trane AUH1B080A9421B installer's manual, p. 4. Written in our own words; check the manual for your exact model.
Add a Z-Wave device at the XL1050
General · ComfortLink II XL1050
Adds a Z-Wave device to the XL1050 bridge. The device must be in learn mode within 4 minutes of pressing ADD DEVICE.
- From the Home screen, select MENU, then SMART HOME.
- Select ADD DEVICE.
- Within 4 minutes, put the Z-Wave device into learn mode using the device maker's instructions.
Applies to: XL1050 Z-Wave bridge
Source: Trane ComfortLink II XL1050 user guide 32-5093-04B-EN, p. 27. Written in our own words; check the manual for your exact model.
Add a Z-Wave device through the Trane Home app
General · ComfortLink XL850
An alternative to adding devices at the control. The device still has to be put into add mode within four minutes.
- Open the Trane Home mobile app.
- Select the menu button in the top left corner.
- At the bottom of the slide-out menu, select Connect New Device.
- Select Z-Wave Device.
- When prompted, put the device into add mode using the device maker's instructions within four minutes.
Applies to: XL850 Smart Control with Trane Home app
Source: ComfortLink Trane XL850 Smart Control user guide (032-5091-06C-EN), p. 27. Written in our own words; check the manual for your exact model.
Add a Z-Wave device with the Trane Home app
General · ComfortLink II XL1050
Adds a Z-Wave device through the mobile app. Allow 4 minutes to complete.
- Start the Trane Home app.
- Select the menu button in the top left corner.
- At the bottom of the slide-out menu, select Connect New Device.
- Select Z-Wave Device.
- Put the device into add mode per its maker's instructions within 4 minutes.
Applies to: XL1050 Z-Wave bridge via Trane Home app
Source: Trane ComfortLink II XL1050 user guide 32-5093-04B-EN, p. 28. Written in our own words; check the manual for your exact model.
Add or remove Z-Wave devices from the control
General · ComfortLink XL850
Z-Wave devices are added or removed from the Smart Home menu on the XL850. The device must be put into learn mode within four minutes of pressing the button on the control. Updating the network can generate heavy Z-Wave traffic and can take up to 15 minutes.
- From the Home screen, select MENU, then SMART HOME.
- To add a device, select ADD DEVICE, then put the Z-Wave device into learn mode using the device maker's instructions within four minutes.
- To remove a device, select REMOVE DEVICE, then put the device into learn mode using the device maker's instructions within four minutes.
- To update the bridge network, select UPDATE NETWORK and allow up to 15 minutes.
Applies to: XL850 Smart Control with Z-Wave bridge
Source: ComfortLink Trane XL850 Smart Control user guide (032-5091-06C-EN), p. 26. Written in our own words; check the manual for your exact model.
Compressor protection before cooling operation
General · XR202
Do not run cooling when outdoor temperature is below 55°F. Before the compressor runs, the compressor oil heaters must have been energized for six hours, and the system must have been off for at least five minutes.
- Check outdoor temperature before enabling cooling.
- If it is below 55°F, keep cooling off.
- Confirm the compressor oil heaters have been on for six hours.
- Confirm the system has been off for at least five minutes before the compressor runs.
Applies to: Cooling systems with a compressor and crankcase oil heater
Source: Trane XR202 installation and user guide (18-HD51D1-1C-EN), p. 2. Written in our own words; check the manual for your exact model.
Compressor protection before cooling startup
General · XR102
Protects the compressor when the outdoor temperature is low or the system has just been stopped.
- Do not run the cooling system if outdoor temperature is below 55°F.
- Energize the compressor oil heaters for six hours before the compressor runs.
- Make sure the system has been off for at least five minutes before restarting the compressor.
Applies to: Trane XR102 cooling systems
Source: Trane XR102 Non-Programmable Thermostat Installation and User Guide, p. 2, 4. Written in our own words; check the manual for your exact model.
Connect the XL850 by Ethernet
General · ComfortLink XL850
A wired connection skips the wireless setup screens in the User Setup Wizard.
- Connect a CAT5 cable from the Ethernet jack on the back of the XL850 to the router.
- The control detects the cable and the User Setup Wizard moves to the Trane Home registration screen.
Applies to: XL850 Smart Control, wired connection
Source: Trane XL850 Smart Control user guide, p. 23. Written in our own words; check the manual for your exact model.
Connect to Wi-Fi (standard or WPS)
General · ComfortLink XL850
Two ways to join the home network. Wi-Fi uses the network name and password. WPS uses the router's WPS button and needs no password entry.
- Standard Wi-Fi: go to Home > Menu > Settings > Network > Connect to WiFi Network, select your network, enter the password and select Connect.
- WPS: press the WPS button on the router, then on the XL850 open the Wireless Network screen and select WI-FI PROTECTED SETUP.
- WPS: select Next on the XL850 to finish the connection.
Applies to: XL850 Smart Control, wireless connection
Source: Trane XL850 Smart Control user guide, p. 22. Written in our own words; check the manual for your exact model.
Heat pump configuration must match the system
General · XR302, XR303, TCONT302, TCONT303
Items 1 and 3 of the configuration menu must match the installed heat pump.
- Set item 1 to HP1 or HP2 to match the compressor type.
- Set item 3 (O/B reversing valve) to O or B to match the changeover valve.
- Confirm the dual fuel and aux heat settings after the heat pump items are set.
Applies to: Heat pump systems
Source: TCONT302 and 303 installation and user guide, p. 14, 16. Written in our own words; check the manual for your exact model.
Keep sensor and HVAC wiring apart
General · XR302, XR303, TCONT302, TCONT303
Outdoor or remote sensor wires pick up interference when routed with HVAC wiring.
- Do not run remote sensor wires in the same bundle as HVAC wires.
- Keep sensor wires away from high voltage wiring.
- Ground unused thermostat wires at the indoor unit chassis only.
- Use a shield only if the wiring guidelines cannot be met, and ground one end only.
Applies to: Wired remote sensors and thermostat wiring
Source: TCONT302 and 303 installation and user guide, p. 2, 8. Written in our own words; check the manual for your exact model.
Modify the heating or cooling schedule
General · XR202, TCONT202
Schedule periods are P1/Wake, P2/Leave, P3/Return and P4/Sleep, applied to all days of the week. The factory energy saving schedule is preset.
- Slide the System Switch to Heat (or Cool for the cooling schedule).
- Press Menu, then Next to enter the schedule.
- Set the start time for the period with the up/down buttons while the time icons flash.
- Press Next and set the temperature for the period.
- Press Next to advance through all periods and all days.
- Press Exit at any time to save and return to the home screen.
Applies to: Trane XR202 / TCONT202
Source: 18-HD51D1-1C-EN Installation and User Guide, p. 11. Written in our own words; check the manual for your exact model.
Register the thermostat to a Trane Home account
General · ComfortLink XL850
Links the control to a Trane Home account so it can be run from a smartphone, tablet or computer.
- Go to www.tranehome.com or download the Trane Home app from the Google Play or App Store, then open it.
- Select Sign Up Now to create an account, or log in to an existing account.
- From the app Dashboard, select the Menu icon, then select Connect New Device.
- Select the Trane or American Standard smart thermostat model (824, 850 or 1050) from the drop-down arrow.
- Select Continue.
Applies to: XL850 Smart Control
Source: Trane XL850 Smart Control user guide, p. 24. Written in our own words; check the manual for your exact model.
Register the XL850 to a Trane Home account
General · ComfortLink XL850
Registration links the control to the Trane Home cloud account so it can be run remotely. The registration steps are printed out of order across pages 24 and 25, so they are reordered here.
- On a phone, tablet or PC, set up a Trane Home account, either on the web or in the Trane Home mobile app.
- If the account already exists, log in and go to the device connection step.
- In the app dashboard, open the menu and choose Connect New Device.
- Select the 824, 850 or 1050 model from the Trane or American Standard smart thermostat drop-down.
- Tap Continue.
- Write down the pin code the app generates.
- On the XL850, select Next.
- Enter the pin code in the app and select Next.
- Read the license agreement, then accept or decline it.
- When the app reports success, select Done.
Applies to: XL850 Smart Control
Source: ComfortLink Trane XL850 Smart Control user guide (032-5091-06C-EN), p. 24-25. Written in our own words; check the manual for your exact model.
Remote sensor averaging example
General · XR302, XR303
With a remote indoor sensor, the displayed temperature is a weighted average of the local and remote sensors.
- Weight A2 averages the two sensors (default).
- Weight H4 gives the remote sensor more influence.
- Weight L1 gives the remote sensor less influence.
- Weight is set in Set Schedule by pressing the up and down keys together.
Applies to: TCONT302 / TCONT303 with indoor remote sensor
Source: Trane XR302/XR303 installation and user guide, p. 23. Written in our own words; check the manual for your exact model.
Set current time and day
General · XR202, TCONT202
Time icons flash after first power-up or a reset.
- Press Set Time.
- Use the up/down buttons to set the hour.
- Press Next to set the minutes and day of the week.
- Press Exit when finished.
Applies to: Trane XR202 / TCONT202
Source: 18-HD51D1-1C-EN Installation and User Guide, p. 11. Written in our own words; check the manual for your exact model.
Temperature calibration needs acclimation time
General · ComfortLink II XL1050
The calibration setting needs the control to settle to room conditions first. Readings can be off during that period.
- Before calibrating, let the control sit in the ambient room for at least 1 hour.
- Do not trust the displayed temperature until the acclimation period has passed.
Applies to: XL1050 temperature calibration
Source: XL1050 user guide 32-5093-04B-EN, p. 7. Written in our own words; check the manual for your exact model.
Thermostat location requirements
General · XR102
Mount on an interior wall in a climate-controlled space, away from direct heat and airflow so the sensor reads true room temperature.
- Pick a central spot with good air circulation.
- Keep it away from lamps, sunlight, fireplaces and other radiant heat.
- Do not mount near windows, behind doors, in poorly ventilated alcoves, on outside walls or next to exterior doors.
- Keep it out of direct air from supply registers or ceiling fans.
- Do not mount on a wall with hot or cold water pipes or ductwork.
- Ceiling fan airflow can trap heat in the case and make the displayed temperature read high.
Applies to: Trane XR102
Source: Trane XR102 Non-Programmable Thermostat Installation and User Guide, p. 3-4. Written in our own words; check the manual for your exact model.
Third-party condensate overflow switch and aux heat during defrost
General · XR302, XR303, TCONT302, TCONT303
Wiring notes from the heat pump diagrams.
- Wire a third-party condensate overflow switch between thermostat Y and the airflow control board Y1.
- Connect X2 when aux heat must energize during defrost.
- Check the factory jumper is in place where the diagram shows one.
Applies to: Heat pump systems with variable speed furnace or GAF2-S
Source: TCONT302 and 303 installation and user guide, p. 9, 11. Written in our own words; check the manual for your exact model.
Trane Home connection and device limit
General · ComfortLink II XL1050
The control works with the Trane Home cloud platform for remote access, runtime history, dealer diagnostics and automations. Up to eight Trane smart controls can share one Trane Home account without a monthly fee. Internet service and Trane Home registration are needed.
- Confirm internet service is available at the site.
- Register the control with a Trane Home account.
- Check the number of smart controls on the account does not exceed eight if no monthly fee is wanted.
Applies to: XL1050 with Trane Home
Source: XL1050 user guide 32-5093-04B-EN, p. 2-3. Written in our own words; check the manual for your exact model.
User Setup Wizard order of steps
General · ComfortLink XL850
The wizard walks through screen, layout, schedule, network, Trane Home and weather settings in sequence. Trane Home and weather need an internet connection and registration.
- Set screen brightness, backlight, screen saver and color theme.
- Choose up to two widgets for the home screen.
- Enable or disable scheduling. Disabled scheduling uses 1-Touch Presets.
- If scheduling is enabled, use guided scheduling. If disabled, set heating and cooling targets for Home, Away and Sleep.
- Select the wireless network and enter the password. If the network is not listed, choose Hidden Network and enter the SSID.
- Register with Trane Home.
- Enter the zip code for weather data.
Applies to: XL850 Smart Control
Source: Trane XL850 Smart Control user guide 032-5091-06C-EN, p. 3. Written in our own words; check the manual for your exact model.
Wiring practices
General · XR302, XR303
Keep low-voltage thermostat wiring away from large inductive loads to avoid noise that can cause erratic operation.
- Use 18-gauge color-coded thermostat cable; shielded cable is usually not needed.
- Keep wiring at least one foot from electronic air cleaners, motors, line starters, lighting ballasts and large distribution panels.
- Ground unused thermostat wires only at the indoor unit chassis ground.
- If shielded cable is needed, ground only one end of the shield to the system chassis.
- Keep remote sensor wires out of the same bundle as HVAC wires.
Applies to: TCONT302 / TCONT303
Source: 18-HD48D1-1C-EN installation and user guide, p. 2 and p. 8. Written in our own words; check the manual for your exact model.
Checkout in normal mode
Heat pump · XR402
Verifies the system in normal operation. Minimum cycle delays set during setup will be enforced.
- Cycle the system through each mode with the mode button.
- Raise or lower the setpoint to turn each cycle on and off.
- Check the filter timer, outdoor temperature display and energy saving features against the user's preference.
Applies to: TCONT402AN32DA Comfort Control
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 4. Written in our own words; check the manual for your exact model.
Dual fuel jumper JP1
Heat pump · XR402
When the system type is heat pump and the indoor heater is gas or oil (dual fuel), the JP1 jumper on the control board must be cut.
- Locate JP1 on the control board.
- Cut JP1 for dual fuel applications.
- For dual fuel, the factory BK jumper at the indoor unit is cut or removed as the wiring diagram shows.
Applies to: Dual fuel and heat pump applications
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 3 and p. 5-6. Written in our own words; check the manual for your exact model.
Low-voltage wiring practice
Heat pump · XR103
Wiring and grounding practice for the XR103 low-voltage control wiring.
- Use 18-gauge color-coded thermostat cable. Shielded cable is usually not needed.
- Keep thermostat wiring at least one foot from large inductive loads such as electronic air cleaners, motors, line starters, lighting ballasts and large panels.
- Ground unused thermostat wire at the indoor unit chassis only.
- Use shielded cable only if the wiring guidelines cannot be met, and ground only one end of the shield.
Applies to: XR103 low-voltage wiring
Source: Trane XR103 installation and user guide 18-HD55D1-1C-EN, p. 3. Written in our own words; check the manual for your exact model.
Save setup choices and wait before power is removed
Heat pump · XR402
The control needs about 5 seconds after the last save (step 99, SA) to write setup choices to memory. Losing power earlier can erase the choices.
- After saving at step 99 (SA), wait at least 5 seconds before removing power.
- If the SERVICE icon flashes afterwards, press any key and check or re-enter the setup choices.
Applies to: TCONT402AN32DA Comfort Control
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 3. Written in our own words; check the manual for your exact model.
Verify 24 VAC transformer capacity
Heat pump · XR103
Check the transformer before final commissioning.
- Review the total 24 VAC load on the indoor unit control transformer.
- Confirm the transformer is adequately sized for the thermostat and equipment loads.
Applies to: XR103 with indoor unit control transformer
Source: Trane XR103 installation and user guide 18-HD55D1-1C-EN, p. 3. Written in our own words; check the manual for your exact model.
Other
Everything else worth knowing at the appliance.
Air filter service
Furnace · Gas Heating Systems
Keep the filter clean for efficiency. Use the same size and type as originally supplied.
- Replace disposable filters monthly with the same size as originally supplied.
- During heavy-use seasons, clean or replace the filter twice a month.
- Install the filter with the arrows pointing in the direction of airflow.
- Never operate the unit for heating or cooling with filters removed.
Applies to: Gas heating system
Source: Trane gas heating system owner's information 32-5083-1C-EN, p. 3. Written in our own words; check the manual for your exact model.
Burner box cover reinstallation
Furnace · UH1 / DH1
Use this method when the cover is removed to service the flame sensor, hot surface igniter or orifices.
- Insert the top flange of the front cover under the lip inside the box.
- Rotate the front cover inward, making sure all side flanges are outside the box.
Applies to: Burner box service
Source: Trane 18-CD29D1-11 installer's guide, p. 39. Written in our own words; check the manual for your exact model.
Category IV direct vent classification
Furnace · UH1, DH1
These furnaces are Category IV: positive vent static pressure with flue loss under 17 percent.
- Use a venting system that is gas tight and water tight.
- Direct vent models are approved for manufactured/mobile housing only when used with BAYMFGH100A.
Applies to: All direct vent furnaces
Source: Trane AUH1B080A9421B installer's manual, p. 3. Written in our own words; check the manual for your exact model.
Close coupled return below 36 in
Furnace · UH1/DH1
A close coupled return with the filter directly under a bottom side return is not recommended because of noise.
- If used anyway, attach 1/2 in mesh metal hardware cloth to the inside bottom of the filter grille to protect the technician's hands from the blower.
- Do not install the filter in the return duct directly above a horizontal furnace.
Applies to: Upflow furnaces in horizontal applications
Source: Trane installer's guide 18-CD29D1-11, p. 10. Written in our own words; check the manual for your exact model.
Combustion air and venting protection
Furnace · Gas Heating Systems
Combustion air must be fresh and uncontaminated, and vent openings must stay open to prevent carbon monoxide entering the building.
- Check that all openings in the outside wall around the vent and air intake pipes are sealed.
- Check that vent and air intake terminals are not obstructed in any season.
- Keep paints, varnishes, bleaches, cleaners, softening salts and adhesives away from the unit.
- Keep the area around the unit free of combustible materials, gasoline and flammable vapors.
Applies to: Gas heating system
Source: Trane gas heating system owner's information 32-5083-1C-EN, p. 3. Written in our own words; check the manual for your exact model.
Condensate drain freeze protection
Furnace · UH1 / DH1
A frozen condensate drain shuts the furnace down.
- Use 1/2 in. or larger PVC or CPVC drain piping.
- If the drain runs outside conditioned space, apply UL listed heat tape rated 5 or 6 W/ft at 120 V.
- Use self-regulating or thermostatically controlled heat tape, installed per manufacturer instructions.
- Use a corrosion resistant condensate pump if a pump is required.
- Where the furnace is above a finished ceiling, route the primary drain vent overflow into an auxiliary drain pan.
Applies to: Condensate drain installations
Source: Trane 18-CD29D1-11 installer's guide, p. 32. Written in our own words; check the manual for your exact model.
Corrosive atmosphere and construction debris warning
Furnace · UH1, DH1
Condensate mixed with chlorides or fluorides from paint, varnish, stains, adhesives, cleaners or cement corrodes the heat exchanger quickly.
- Do not install the furnace in a corrosive or contaminated atmosphere.
- Keep the furnace from being used as a construction heater until the construction heater conditions are met.
Applies to: All furnaces
Source: Trane AUH1B080A9421B installer's manual, p. 4 and p. 3. Written in our own words; check the manual for your exact model.
Do not use field fabricated venting parts
Furnace · UH1 / DH1
Only factory supplied venting components may be used. Field fabricated parts can damage the vent and cause carbon monoxide poisoning or death.
- Use only factory supplied venting components.
- Do not run return air through the side of the furnace cabinet on horizontal applications.
Applies to: All venting installations
Source: Trane AUH1B080A9421B installer's manual, p. 24. Written in our own words; check the manual for your exact model.
Downflow filter brackets and horizontal filter location
Furnace · UH1/DH1
Downflow furnaces come with factory brackets to mount filters in the return duct. Horizontal filters must be placed remotely, not in the return duct directly above the furnace.
- Mount the factory brackets to hold the filter in the return duct.
- Locate the filter remotely from the furnace in horizontal applications.
Applies to: DH1 downflow and horizontal installs
Source: Trane installer's guide 18-CD29D1-11, p. 10. Written in our own words; check the manual for your exact model.
Flexible connectors and vibration
Furnace · UH1/DH1
Flexible nonflammable connectors reduce transmission of vibration, which can amplify noise through ducts.
- Use flexible connectors on return and discharge connections.
- Use removable plenums if only the front is accessible.
Applies to: All UH1/DH1 furnaces
Source: Trane installer's guide 18-CD29D1-11, pp. 9-10. Written in our own words; check the manual for your exact model.
Gas leak testing method
Furnace · UH1, DH1
Do not check for leaks with an open flame.
- Check all gas connections with a commercial leak-detection soap solution.
- See the Gas Piping section (pages 31-32) for the full procedure.
Applies to: All furnaces
Source: Trane AUH1B080A9421B installer's manual, p. 6. Written in our own words; check the manual for your exact model.
Owner shutdown warnings
Furnace · UH1 / DH1
Advise the owner on gas shutoff and freeze protection.
- If electrical, fuel or mechanical failure occurs, shut off the manual gas valve before turning off electrical power.
- During cold weather shutdowns, protect water pipes and receptacles from freezing.
- Contact the designated service agency for failures.
Applies to: Owner instructions
Source: Trane 18-CD29D1-11 installer's guide, p. 36. Written in our own words; check the manual for your exact model.
Propane gas hazard and gas detector
Furnace · UH1, DH1
Propane is heavier than air and can collect in low areas or confined spaces. Odorant can fade, so a leak may not be noticed by smell.
- If the furnace is in a basement, excavated area or confined space, recommend the customer have the gas supplier install a gas detecting warning device.
- The manufacturer does not test or endorse any detector brand.
Applies to: Propane-fired furnaces in low or confined spaces
Source: Trane AUH1B080A9421B installer's manual, p. 4. Written in our own words; check the manual for your exact model.
Propane is heavier than air and odorant can fade
Furnace · UH1/DH1
A gas leak can collect in low areas or confined spaces, and odorant can fade so the leak is not noticed. A gas detecting warning device is strongly recommended for basement, excavated or confined installs.
- Recommend that the customer contact a gas supplier to install a gas detecting warning device.
- Note that the manufacturer does not test detectors and makes no claim about any brand.
Applies to: Propane gas furnaces in basements or confined spaces
Source: Trane installer's guide 18-CD29D1-11, p. 8. Written in our own words; check the manual for your exact model.
Shut off gas supply during failure
Furnace · AUH1B
If electrical, fuel or mechanical failure occurs, close the gas supply before removing electrical power.
- Turn off the gas at the manual gas valve on the supply piping.
- Then turn off electrical power to the furnace.
- Contact the designated service agency.
Applies to: AUH1B furnaces
Source: Trane installer's manual (AUH1B040A9241A), p. 40. Written in our own words; check the manual for your exact model.
Turn off power before servicing filters
Furnace · UH1/DH1
Moving parts can cause injury or death, so power must be off before servicing the filter.
- Switch the furnace power off before removing or changing the filter.
Applies to: All UH1/DH1 furnaces
Source: Trane installer's guide 18-CD29D1-11, p. 10. Written in our own words; check the manual for your exact model.
Upflow 5 or 6 ton above 1800 CFM needs multiple return openings
Furnace · UH1/DH1
On upflow 5 or 6 ton airflow models where required airflow exceeds 1800 CFM, return air openings and filters are needed on both sides, on one side and the bottom, or on the bottom only.
- Confirm return openings and filters are provided per one of the three allowed layouts.
- Use the Table 5 filter sizes for the cabinet width.
Applies to: Upflow 5 or 6 ton airflow models
Source: Trane installer's guide 18-CD29D1-11, pp. 8-9. Written in our own words; check the manual for your exact model.
Wiring basis for a one-stage heating system
Furnace · AUH1B, UH1, DH1
The field wiring example shown is for a one-stage heating thermostat with no cooling. Supply is 115 V, single phase, 60 Hz, per local codes.
- Wire to 115 V, 1 phase, 60 Hz per local codes.
- Use a one-stage heating thermostat with no cooling for this wiring example.
- Check the wiring diagram on p. 28 for the humidifier and EAC connections.
Applies to: One-stage heating furnace wiring
Source: Trane installer's guide, p. 28. Written in our own words; check the manual for your exact model.
Add a period to a day
General · ComfortLink XL850
Each day can have from 1 to 4 periods, and each day can have a different number of periods.
- Select ADD PERIOD on the Schedule Screen.
- Select the green circle where the new period should start.
- Choose a predefined name, or select New, enter a name, and select NEXT.
- Add more periods if needed; the maximum is 4 per day.
- Select APPLY to save and return to the Schedule Screen.
Applies to: XL850 Smart Control
Source: ComfortLink Trane XL850 Smart Control User Guide (032-5091-06C-EN), p. 15. Written in our own words; check the manual for your exact model.
Automatic software updates
General · ComfortLink II XL1050
Updates install automatically when the XL1050 is connected to Trane Home. They need internet service.
Applies to: XL1050 connected to Trane Home
Source: Trane ComfortLink II XL1050 user guide 32-5093-04B-EN, p. 30. Written in our own words; check the manual for your exact model.
Battery installation and replacement
General · XR203
The thermostat uses two AA alkaline batteries. Premium AA alkaline batteries are required when no C-wire is available. With a C-wire, the batteries act as backup to keep the clock running during a power outage.
- Set the system to OFF before replacing batteries.
- Remove the thermostat from the wall.
- Install AA batteries in the rear along the bottom of the thermostat.
- Use a premium alkaline brand such as Duracell or Energizer.
- Replace batteries before leaving an unoccupied home for more than 3 months if the low-battery symbol is showing.
Applies to: XR203 power supply
Source: Trane XR203 Installation and User Guide 18-HD50D1-1D-EN, p. 4. Written in our own words; check the manual for your exact model.
Battery level and battery warnings
General · XR302, XR303, TCONT302, TCONT303
The display shows battery power for the two AA batteries.
- Full bars: full power remaining.
- Half bars: about half power remaining.
- Change indicator: replace the batteries now.
- If the home will be unoccupied over 3 months, replace batteries before leaving.
Applies to: Battery powered thermostat
Source: TCONT302 and 303 installation and user guide, p. 13. Written in our own words; check the manual for your exact model.
Battery replacement
General · XR302, XR303
Replace the two AA alkaline batteries with the system switched off. A premium alkaline brand is recommended. If the home will be empty for over 3 months, replace batteries before leaving.
- Set the system to OFF.
- Remove the thermostat from the wall plate.
- Install two AA alkaline batteries in the rear, along the top of the thermostat.
- Reseat the thermostat on the base.
Applies to: TCONT302 / TCONT303
Source: 18-HD48D1-1C-EN installation and user guide, p. 4. Written in our own words; check the manual for your exact model.
Call for Service indicator
General · XR302, XR303, TCONT302, TCONT303
Call for Service shows a fault in the heating or cooling equipment. It does not mean the thermostat has failed.
- Check the heating or cooling equipment first.
- Contact the HVAC service person if the equipment has a fault.
Applies to: TCONT302 / TCONT303
Source: TCONT302 and 303 installation and user guide, p. 13. Written in our own words; check the manual for your exact model.
Caution: compressor oil heater and cooling lockout
General · XR302, XR303
Compressor can be damaged if run too soon or in low ambient.
- Do not run the compressor until oil heaters have been on for 6 hours.
- Do not run compressor until the system has been off at least 5 minutes.
- Do not run cooling if outdoor temperature is below 55°F.
Applies to: Heat pump and AC compressors
Source: Trane XR302/XR303 installation and user guide, p. 19. Written in our own words; check the manual for your exact model.
Change a period heating or cooling set point
General · ComfortLink XL850
Set points are changed per period for heating and cooling.
- Select the active period's Cooling or Heating Set Point.
- Adjust it with the UP or DOWN arrows.
- Select APPLY to save.
Applies to: XL850 Smart Control
Source: ComfortLink Trane XL850 Smart Control User Guide (032-5091-06C-EN), p. 14. Written in our own words; check the manual for your exact model.
Change a period start or end time
General · ComfortLink XL850
The control blocks illogical times. Each period must be at least 30 minutes long.
- Select anywhere in the period to make it active.
- Select TIME START or TIME END.
- Adjust the time with the UP and DOWN arrows.
- Select APPLY to save, or CANCEL to discard all changes to this schedule.
Applies to: XL850 Smart Control
Source: ComfortLink Trane XL850 Smart Control User Guide (032-5091-06C-EN), p. 14. Written in our own words; check the manual for your exact model.
Copy one day's schedule to other days
General · ComfortLink XL850
Copy a schedule by grouping days first, then removing the target days from the group.
- Group the days so they share the same schedule.
- Select Apply.
- Open the grouping menu again and de-select the days that should get the copy.
- Select Apply again.
Applies to: XL850 Smart Control
Source: ComfortLink Trane XL850 Smart Control User Guide (032-5091-06C-EN), p. 13. Written in our own words; check the manual for your exact model.
Delete a period from a day
General · ComfortLink XL850
Each day must keep at least one period, so the last period cannot be removed.
- Select DELETE PERIOD on the Schedule Screen.
- Select the trash can icon on each period to remove.
- Select APPLY to save and return to the Schedule Screen.
Applies to: XL850 Smart Control
Source: ComfortLink Trane XL850 Smart Control User Guide (032-5091-06C-EN), p. 16. Written in our own words; check the manual for your exact model.
Display symbols (heat, cool, lockout, low battery)
General · XR102
The symbols are shown in the manual as icons that did not extract. Their meanings are: heat mode symbol shows when SYSTEM is on HEAT; cool mode symbol shows steady when SYSTEM is on COOL; a flashing cool symbol means the compressor is in lockout (5-minute minimum off time); a low battery symbol with nothing else shown means the two AAA batteries need replacing; the set temperature area is blank when SYSTEM is OFF.
- If the flashing lockout symbol shows, wait for the 5-minute minimum off time to clear.
- If the low battery symbol shows, replace both AAA alkaline batteries.
Applies to: All XR102 thermostats
Source: Trane XR102 installation and user guide, p. 9. Written in our own words; check the manual for your exact model.
Enable Quiet Mode
General · ComfortLink II XL1050
Quiet Mode limits compressor operation to minimum speed from 10 p.m. to 9 a.m. It applies only to VSPD (TruComfort variable speed) systems with an XL1050 control. It is disabled by default. Heating may use indoor heat if the system cannot hold setpoint.
- From the Home screen, select SYSTEM MODE.
- Select SYSTEM OPTIONS.
- Select ENABLE.
- Confirm QUIET shows below the indoor temperature on the home screen.
Applies to: XL1050 with VSPD variable speed system
Source: Trane ComfortLink II XL1050 user guide 32-5093-04B-EN, p. 30. Written in our own words; check the manual for your exact model.
Filter, humidifier pad and UV lamp reminders
General · XR302, XR303, TCONT302, TCONT303
The display shows Change Filter, Change Pad or Change UV Lamp after the programmed run time.
- Clean or replace the filter when Change Filter shows.
- Clean or replace the humidity pad when Change Pad shows (model 303).
- Replace the UV lamp when Change UV Lamp shows (model 303).
Applies to: TCONT302 / TCONT303
Source: TCONT302 and 303 installation and user guide, p. 13, 15. Written in our own words; check the manual for your exact model.
Front panel controls
General · XR102
Up and down arrows change the setpoint. The FAN switch selects ON or AUTO. The SYSTEM switch selects COOL, OFF or HEAT.
Applies to: All XR102 thermostats
Source: Trane XR102 installation and user guide, p. 9. Written in our own words; check the manual for your exact model.
Home screen basics
General · ComfortLink II XL1050
Out of the box the home screen is a basic thermostat view and scheduling is off. Change the setpoint with the HEAT TO or COOL TO controls; it holds that temperature until changed again. Use the SYSTEM or FAN MODE buttons to pick operation.
- Press HEAT TO or COOL TO and raise or lower the setpoint.
- Press the SYSTEM button to choose Auto, Heating, Cooling, Off or Emergency Heat.
- Press the FAN MODE button to choose Auto, On or Circulate.
Applies to: XL1050 home screen
Source: XL1050 user guide 32-5093-04B-EN, p. 4-5. Written in our own words; check the manual for your exact model.
Home screen customization options
General · ComfortLink II XL1050
The default home screen lets you show up to 3 of 7 available widgets. With scheduling enabled, a schedule can be built with the Scheduling Wizard. In the Default configuration you can also set up 3 presets (Home, Away, Sleep) that change heating and cooling settings with one button.
- Go to the home screen customization setup.
- Select up to 3 of the 7 widgets to display.
- Optionally set up the Home, Away and Sleep presets with one button each.
Applies to: XL1050 home screen
Source: XL1050 user guide 32-5093-04B-EN, p. 8-10. Written in our own words; check the manual for your exact model.
Home screen mode, fan and preset controls
General · ComfortLink XL850
Quick controls on the home screen. The Classic View also shows the air cleaner control.
- System mode: Auto, Heating, Cooling, Off or Emergency Heat.
- Fan mode: Auto, On or Circulate.
- Air cleaner mode (Classic View): On or Off.
- 1-Touch presets: Off, Home, Away or Sleep.
- Use the set point up and down arrows to change the target temperature.
Applies to: XL850 Smart Control
Source: Trane XL850 Smart Control user guide 032-5091-06C-EN, p. 4, p. 6. Written in our own words; check the manual for your exact model.
Live electrical work warning
General · XR203
Expect live components during install, test and troubleshooting. Do not connect the thermostat to circuits above the rated voltage, and never short the gas valve or primary control terminals to test. A short or wrong wiring will burn out the thermostat.
- Turn off power at the main fuse or breaker before installing.
- Confirm the circuit voltage is within the 20-30 VAC rating before connecting.
- Never jumper gas valve or primary control terminals to test.
Applies to: All XR203 installations
Source: Trane XR203 Installation and User Guide 18-HD50D1-1D-EN, p. 2. Written in our own words; check the manual for your exact model.
Low battery effects and battery replacement
General · XR102
When batteries are low, the display goes blank except for the low battery symbol. Pressing a button shows the display for about ten seconds. If the low battery symbol has been showing for 4 weeks, the thermostat moves the temperature 10 degrees past the setpoint (up in COOL, down in HEAT). Replace batteries once a year with new premium alkaline AAA batteries.
- Replace both AAA alkaline batteries as soon as the low battery symbol appears.
- Replace batteries once a year as routine maintenance.
- Install new batteries before leaving a home unoccupied for a long period.
Applies to: All XR102 thermostats
Source: Trane XR102 installation and user guide, p. 10 and p. 11. Written in our own words; check the manual for your exact model.
RC/RH jumper
General · XR203
The thermostat ties RC and RH together internally, so a jumper wire is not needed. If the system provides separate RC and RH wires, clip the RC/RH jumper to isolate the two terminals so they can be used independently.
- Check whether the system has separate RC and RH wires.
- If it does, clip the RC/RH jumper on the thermostat.
Applies to: XR203 with separate RC and RH wiring
Source: Trane XR203 Installation and User Guide 18-HD50D1-1D-EN, p. 4. Written in our own words; check the manual for your exact model.
Remove a Z-Wave device
General · ComfortLink II XL1050
Removes a Z-Wave device from the bridge. The device must be in learn mode within 4 minutes of pressing REMOVE DEVICE.
- From the Home screen, select MENU, then SMART HOME.
- Select REMOVE DEVICE.
- Within 4 minutes, put the Z-Wave device into learn mode using the device maker's instructions.
Applies to: XL1050 Z-Wave bridge
Source: Trane ComfortLink II XL1050 user guide 32-5093-04B-EN, p. 27. Written in our own words; check the manual for your exact model.
Rename a period
General · ComfortLink XL850
Periods can use a preset name or a custom name typed on the on-screen keyboard.
- Select the PERIOD NAME (for example Wake or Away).
- Select a predefined name, or select NEW and then NEXT to type a custom name.
- Select NEXT and then APPLY.
Applies to: XL850 Smart Control
Source: ComfortLink Trane XL850 Smart Control User Guide (032-5091-06C-EN), p. 14. Written in our own words; check the manual for your exact model.
Scheduling override and resume
General · ComfortLink II XL1050
With scheduling enabled the Preset button is replaced by Permanent Hold. Temperature changes made with the arrows override the schedule only until the next period change.
- Use the up and down arrows at the right of the screen to override the current temperature.
- Wait for the next schedule period change. The schedule resumes automatically.
Applies to: XL1050 with scheduling enabled
Source: 32-5093-04B-EN XL1050 user guide, p. 10. Written in our own words; check the manual for your exact model.
Scroll between zones on multi-zone systems
General · ComfortLink II XL1050
On a multi-zone system the home screen shows one zone at a time.
- Press the arrow keys to scroll between zones.
Applies to: XL1050 on multi-zone systems
Source: 32-5093-04B-EN XL1050 user guide, p. 10. Written in our own words; check the manual for your exact model.
Short-cycle protection delay
General · XR203
The thermostat delays restarts to protect the equipment from short cycling. The icon shows during this 5-minute delay.
- Wait for the 5-minute delay to end before expecting the system to restart
Applies to: Trane XR203 thermostat
Source: Trane XR203 installation and user guide, p. 16. Written in our own words; check the manual for your exact model.
Thermostat wiring practice
General · XR203
Use 18-gauge color-coded thermostat cable. Shielded cable is usually not required. Keep low-voltage wiring at least one foot from large inductive loads such as electronic air cleaners, motors, line starters, ballasts and large panels to avoid noise and erratic operation.
- Use 18-gauge color-coded thermostat wire.
- Route thermostat wire at least one foot away from large inductive loads.
- Ground unused thermostat wires only at the indoor unit chassis ground.
- If shielding is needed, ground only one end of the shield to the system chassis.
Applies to: All XR203 low-voltage wiring
Source: Trane XR203 Installation and User Guide 18-HD50D1-1D-EN, p. 3. Written in our own words; check the manual for your exact model.
Third-party condensate overflow switch wiring
General · XR203
On heat pump and heat/cool packages, a third-party condensate overflow switch is wired between the thermostat Y terminal and the Y1 terminal of the airflow control board.
- Wire the third-party condensate overflow switch between thermostat Y and airflow control board Y1.
Applies to: Heat pump and heat/cool package wiring with variable or non-variable speed blower
Source: Trane XR203 installation and user guide, p. 8. Written in our own words; check the manual for your exact model.
Update the Z-Wave network
General · ComfortLink II XL1050
A network update creates heavy Z-Wave traffic and can take up to 15 minutes.
- From the Smart Home screen, select UPDATE NETWORK.
- Allow up to 15 minutes to finish.
Applies to: XL1050 Z-Wave bridge
Source: Trane ComfortLink II XL1050 user guide 32-5093-04B-EN, p. 27. Written in our own words; check the manual for your exact model.
Wired network connection skips Wi-Fi setup
General · ComfortLink XL850
Wireless setup is not needed when the control is hard-wired to the home network.
Applies to: XL850 Smart Control
Source: Trane XL850 Smart Control user guide 032-5091-06C-EN, p. 3. Written in our own words; check the manual for your exact model.
X2 required for auxiliary heat during defrost
General · XR102
The X2 connection must be wired to energize auxiliary heat during defrost.
- Make sure X2 is wired when the system needs auxiliary heat to run during defrost.
Applies to: Cooling with GAT2, GAM2 & TEM3, 4 wiring
Source: Trane XR102 installation and user guide, p. 8. Written in our own words; check the manual for your exact model.
X2 wire for auxiliary heat during defrost
General · XR203
On heat pump wiring diagrams the X2 connection is needed to energize auxiliary heat during defrost.
- Connect X2 on heat pump installs so auxiliary heat runs during defrost.
Applies to: Heat pump wiring with auxiliary heat
Source: Trane XR203 installation and user guide, p. 8. Written in our own words; check the manual for your exact model.
Z-Wave bridge
General · ComfortLink II XL1050
The XL1050 has a built-in Z-Wave bridge and can connect to over 200 Z-Wave devices through Trane Home. Z-Wave device adding and removal is handled from the Trane Home section of the menu.
- Use the Z-Wave section in the menu to add or remove devices.
- Add devices through the mobile app when the app method is used.
Applies to: XL1050 Z-Wave
Source: XL1050 user guide 32-5093-04B-EN, p. 2, 6. Written in our own words; check the manual for your exact model.
Balance point definitions for heat pump changeover
Heat pump · XR402
Economic balance point is the outdoor temperature where the alternate fuel is cheaper to run than the heat pump. Application balance point is the outdoor temperature below which the heat pump alone cannot meet the load. The Restricted Mode changeover must be set at or above the application or economic balance point.
- Set the Heat Pump Restricted Mode outdoor temperature at or above the system's economic or application balance point.
Applies to: Heat pump with fossil fuel auxiliary heat
Source: 18-HD29D3-4 installer's guide, p. 17. Written in our own words; check the manual for your exact model.
Battery service and low-battery indication
Heat pump · XR103
Batteries keep the configuration memory if AC power is lost.
- Install two new premium AAA alkaline batteries along the bottom of the thermostat.
- Install the batteries with the positive (+) ends to the right.
- Replace all batteries together when BATT appears, and before leaving the house unoccupied for a long time.
Applies to: XR103 thermostat
Source: Trane XR103 installation and user guide 18-HD55D1-1C-EN, p. 4 and 8. Written in our own words; check the manual for your exact model.
Business card drawer
Heat pump · XR402
The drawer on the mounting base holds the servicer's business card so the homeowner has a contact for service calls.
- Fold a standard business card and slide it into the slot on the drawer.
Applies to: TCONT402AN32DA mounting base
Source: 18-HD29D3-4 installer's guide, p. 16. Written in our own words; check the manual for your exact model.
Compressor protection in cold weather
Heat pump · XR203
Below 55°F outdoor temperature, do not run cooling. Compressor oil heaters must have been energized for six hours, and the system must have been off for at least five minutes before the compressor is allowed to run.
- Check outdoor temperature before enabling cooling.
- If outdoor temperature is under 55°F, keep cooling locked out.
- Confirm compressor oil heaters have run six hours before starting the compressor.
- Allow at least five minutes off between compressor runs.
Applies to: Heat pump and cooling systems with compressor oil heaters
Source: Trane XR203 Installation and User Guide 18-HD50D1-1D-EN, p. 2. Written in our own words; check the manual for your exact model.
Discharge static before touching keys
Heat pump · XR103, TCONT103
Static build-up can cause erratic operation.
- Touch the side of the thermostat to release static before pressing any keys.
Applies to: XR103 / TCONT103
Source: Trane TCONT103 installation and user guide, p. 9. Written in our own words; check the manual for your exact model.
Do not short gas valve or primary control terminals to test
Heat pump · XR103
Shorting or incorrect wiring at these terminals can burn out the thermostat.
- Do not short the terminals on the gas valve or primary control to test.
- Confirm wiring against the correct diagram before power-up.
Applies to: Heat pump systems with gas valve or primary control
Source: Trane XR103 installation and user guide 18-HD55D1-1C-EN, p. 2. Written in our own words; check the manual for your exact model.
Emergency heat fan wiring decision
Heat pump · XR103
Jumper W906 decides whether the emergency or auxiliary heat or the thermostat energizes the blower.
- Cut W906 if the emergency or auxiliary heat system energizes the blower.
- Leave W906 intact if the thermostat must energize the fan circuit.
Applies to: XR103 with emergency or auxiliary heat
Source: Trane XR103 installation and user guide 18-HD55D1-1C-EN, p. 4. Written in our own words; check the manual for your exact model.
Mount the comfort control
Heat pump · XR402
Place the control where it reads room temperature correctly and away from heat sources and drafts.
- Mount about 60 in (1.5 m) above the floor on an interior partition wall.
- Do not mount on an outside wall.
- Keep it out of direct sun, away from lamps, fireplaces and other radiant heat.
- Keep it away from windows, doors, alcoves with poor airflow, and supply registers.
- Do not mount it on a wall that has hot or cold water pipes or ductwork.
- Turn off power before wiring and turn it back on after the control is reinstalled.
Applies to: TCONT402AN32DA Comfort Control
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 2. Written in our own words; check the manual for your exact model.
Outdoor sensor location and wiring
Heat pump · XR402
Outdoor sensor must give steady, accurate readings.
- Mount on the north-facing side of the building, in free airflow and out of direct sun.
- Keep it away from attic hot air, drafts from exterior walls, dryer vents and the outdoor unit's condenser fan discharge.
- Seal the wall penetration with non-hardening caulk, putty or insulation.
- Use at least 18 AWG wire, with a maximum run of 200 feet.
Applies to: Outdoor temperature sensor
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 2. Written in our own words; check the manual for your exact model.
Outdoor temperature sensor use
Heat pump · XR402
With the outdoor sensor installed and enabled, the outdoor temperature shows on the display when Filter/OD is pressed. The sensor is also required for Cooling Efficiency Booster, Heat Pump Restricted Mode, Heating Aggressive Recovery, Auxiliary Heat Lockout and Defrost Heater Balance Point control.
- Install and enable the outdoor sensor in the installer setup.
- Press Filter/OD to confirm the outdoor reading on the display.
Applies to: TCONT402AN32DA with outdoor sensor
Source: 18-HD29D3-4 installer's guide, p. 16. Written in our own words; check the manual for your exact model.
Remote indoor sensor fallback
Heat pump · XR402
With the remote indoor sensor enabled, the control displays and controls on the remote reading without moving the thermostat. If the remote sensor fails, control reverts to the on-board sensor, so the thermostat must still be installed in the conditioned space.
- Confirm the remote indoor sensor is installed and enabled.
- Confirm the thermostat is mounted in the conditioned space.
Applies to: TCONT402AN32DA with remote indoor sensor
Source: 18-HD29D3-4 installer's guide, p. 16. Written in our own words; check the manual for your exact model.
SERVICE indicator for internal faults
Heat pump · XR402
The SERVICE indicator flashes when the control detects an internal fault or error.
- When SERVICE flashes, press any key.
- Check the installer setup choices and re-enter any that are wrong.
Applies to: TCONT402AN32DA Comfort Control
Source: 18-HD29D3-4 installer's guide, p. 16. Written in our own words; check the manual for your exact model.
Service indicator meaning
Heat pump · XR402
The SERVICE indicator flashes when the control detects an internal fault or error. Flashing or solid SERVICE with a fault pattern is covered in the troubleshooting guides.
- Note what else is shown on the display (flashing pattern, dashes, Heat or ROOM icons).
- Match the pattern with the troubleshooting table.
- Check and re-enter setup choices if the EEPROM write error is the cause.
Applies to: XR402 Comfort Control
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 16, 14. Written in our own words; check the manual for your exact model.
Waiting indicator during time delays
Heat pump · XR402
The Waiting indicator lights when the setpoint is moved toward calling for more capacity. It means the system time delays are being enforced while the control adjusts to the new setting.
- Leave the system alone until the Waiting indicator turns off.
- Do not treat the delay as a fault unless it lasts longer than the normal minimum off time.
Applies to: TCONT402AN32DA Comfort Control
Source: 18-HD29D3-4 installer's guide, p. 16. Written in our own words; check the manual for your exact model.
Related
Same tips in your pocket
The HVACopedia app has these tips, every error code and the settings tables offline.
For licensed technicians. Installer menus, test modes and access codes change settings that affect safety; only use them if you are trained on the appliance and understand the result. Gas, electrical and refrigerant work must be done by a qualified, licensed person, and the manufacturer’s manual for the exact model and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.