Emergency heat (EM) sequence, heat pump only

XR302XR303

What happens, in order

  1. Press SYSTEM to select EM; 'EM Heat Mode' flashes.
  2. Set setpoint above room temperature; emergency heat starts and display shows 'System On' with 'EM Heat Mode' and 'Heat'.
  3. Raise setpoint 3° above room; additional aux stages start and display shows 'System On +2'.
  4. Lower setpoint below room temperature to stop.

Codes you may see during this

EM Heat Mode System On +2

Applies to: HP1/HP2 emergency heat, uses W/E and W2

Models

TCONT302TCONT303

More Trane heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane XR302/XR303 installation and user guide, p. 19. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.