Trane · Heat pump · Heating
Heat pump heating sequence and aux stage
What happens, in order
- Press SYSTEM to select HEAT.
- Set the setpoint 1° above room temperature.
- Heat starts if the compressor lockout time is met; otherwise the setpoint flashes.
- 'System On' shows when heating starts.
- Raise setpoint 3° above room; aux heat starts and display shows 'System On +2' (MS2, HP1 or HP2).
- Lower setpoint below room temperature to stop heating.
Timings and thresholds
| Item | Value |
|---|---|
| Compressor lockout minimum OFF time | 5 minutes |
| Compressor delay after aux heat on (Cd) | 60 seconds default, 0-99 s |
Codes you may see during this
System On System On +2
Applies to: HP1/HP2 and MS2 heat
Models
More Trane heat pump sequences
- Fan check · Startup
- Dual fuel transition from furnace to heat pump · Heating
- Emergency heat (EM) sequence, heat pump only · Heating
- Emergency heat sequence · Heating
- Heat pump heating sequence · Heating
- Heat pump low-temperature fallback to aux · Heating
- Heat pump warm air discharge · Heating
- Restricted mode heating (heat pump first, furnace above balance point limit) · Heating
Related
Trane error codes · Trane tips · Trane parts · All Trane sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Trane XR302/XR303 installation and user guide, p. 19 and 17. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.