Trane · Heat pump · Heating
Heat pump heating sequence
What happens, in order
- Set the SYSTEM switch to HEAT. Light the auxiliary pilot if one is fitted.
- Set the setpoint about 1° above room temperature. The heat pump starts.
- If the flame and snowflake icons flash, compressor lockout is active and the heat pump waits.
- Set the setpoint about 4° above room temperature. The auxiliary heat starts and the flame icon flashes.
- Set the setpoint below room temperature. Heating stops.
Timings and thresholds
| Item | Value |
|---|---|
| Compressor lockout delay (CL ON) | 5 minutes |
| Lockout icon flashing | about 5 minutes |
| Second stage delay with FA OFF | more than 10 minutes at 1°F or more above actual |
Codes you may see during this
Applies to: Heat pump with furnace or auxiliary heat
Models
More Trane heat pump sequences
- Fan check · Startup
- Dual fuel transition from furnace to heat pump · Heating
- Emergency heat (EM) sequence, heat pump only · Heating
- Emergency heat sequence · Heating
- Heat pump heating sequence and aux stage · Heating
- Heat pump low-temperature fallback to aux · Heating
- Heat pump warm air discharge · Heating
- Restricted mode heating (heat pump first, furnace above balance point limit) · Heating
Related
Trane error codes · Trane tips · Trane parts · All Trane sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Trane TCONT103 installation and user guide, p. 9. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.